FC 300 Operating Instructions
General Specifications
Control characteristics:
Resolution of output frequency at 0 - 1000 Hz .................... FC 301: +/- 0.013 Hz / FC 302: +/- 0.003 Hz
Repeat accuracy of
Precise start/stop
(terminals 18, 19) .......... FC 301: ≤ ± 1ms / FC 302: ≤ ± 0.1 msec
System response time (terminals 18, 19, 27, 29, 32, 33) ..................
FC 301: ≤ 20 ms / FC 302: ≤ 2 ms
Speed control range (open loop) ............................................................... 1:100 of synchronous speed
Speed control range (closed loop) ........................................................... 1:1000 of synchronous speed
Speed accuracy (open loop) .................................................. 30 - 4000 rpm: Maximum error of ±8 rpm
Speed accuracy (closed loop) ............................................. 0 - 6000 rpm: Maximum error of ±0.15 rpm
All control characteristics are based on a 4-pole asynchronous motor
Surroundings:
Enclosure ............................................................................................................................... IP 20
Enclosure kit available ..................................................................................... IP21/TYPE 1/IP 4X top
Vibration test .......................................................................................................................... 1.0 g
Max. relative humidity ................... 5% - 95%(IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 721-3-3), uncoated .................................................................
class 3C2
Aggressive environment (IEC 721-3-3), coated ....................................................................
class 3C3
Ambient temperature .................................................... Max. 50 °C (24-hour average maximum 45 °C)
Derating for high ambient temperature, see special conditions in the Design Guide
Minimum ambient temperature during full-scale operation ............................................................
0 °C
Minimum ambient temperature at reduced performance ...........................................................
- 10 °C
Temperature during storage/transport ........................................................................ -25 - +65/70 °C
Maximum altitude above sea level .......................................................................................... 1000 m
Derating for high altitude, see special conditions in the Design Guide
EMC standards, Emission ...............................
EN 61800-3, EN 61000-6-3/4, EN 55011, (EN 50081-1/2)
EMC standards, Immunity ....................................................................
EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, (EN 50082-1/2)
See section on special conditions in the Design Guide
Protection and Features:
•
Electronic thermal motor protection against overload.
•
Temperature monitoring of the heatsink ensures that the trips if the temperature reaches 95 °C ± 5°C.
An overload temperature cannot be reset until the temperature of the heatsink is below 70 °C ± 5°C.
•
The frequency converter is protected against short-circuits on motor terminals U, V, W.
•
If a mains phase is missing, the frequency converter trips or issues a warning.
•
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the
intermediate circuit voltage is too low or too high.
•
The frequency converter is protected against earth faults on motor terminals U, V, W.
51