Input resistance, R
i
...................................................................................................... approx. 4 kΩ
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
2) Terminal 37 is only available in FC 302. It can only be used as “safe stop” input. Terminal 37 is suitable
for category 3 installations according to EN 954-1 (safe stop according to category 0 EN 60204-1).
3) Exception: Terminal 37 is fixed PNP logic.
Analogue inputs:
Number of analogue inputs ............................................................................................................. 2
Terminal number ................................................................................................................... 53, 54
Modes ................................................................................................................. Voltage or current
Mode select .......................................................................................... Switch S201 and switch S202
Voltage mode .............................................................................. Switch S201/switch S202 = OFF (U)
Voltage level ....................................................... FC 301: 0 to + 10 / FC 302: -10 to +10 V (scaleable)
Input resistance, R
i
.................................................................................................... approx. 10 kΩ
Max. voltage ........................................................................................................................ ± 20 V
Current mode ................................................................................ Switch S201/switch S202 = ON (I)
Current level ............................................................................................... 0/4 to 20 mA (scaleable)
Input resistance, R
i
.................................................................................................... approx. 200 Ω
Max. current ........................................................................................................................ 30 mA
Resolution for analogue inputs ..................................................................................... 10 bit (+ sign)
Accuracy of analogue inputs .................................................................... Max. error 0.5% of full scale
Bandwidth ........................................................................................ FC 301: 20 Hz / FC 302: 100 Hz
The analogue inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage
terminals.
Pulse/encoder inputs:
Programmable pulse/encoder inputs ............................................................................................. 2/1
Terminal number pulse/encoder ........................................................................ 29, 33
1)
/ 18, 32, 33
2)
Max. frequency at terminal 18, 29, 32, 33 .................................................... 110 kHz (Push-pull driven)
Max. frequency at terminal 18, 29, 32, 33 ........................................................... 5 kHz (open collector)
Min. frequency at terminal 18, 29, 32, 33 ................................................................................... 4 Hz
Voltage level ............................................................................................. see section on Digital input
Maximum voltage on input ................................................................................................... 28 V DC
Input resistance, R
i
..................................................................................................... approx. 4 kΩ
Pulse input accuracy (0.1 - 1 kHz) ..........................................................
Max. error: 0.1% of full scale
Encoder input accuracy (1 - 110 kHz) ..................................................
Max. error: 0.05 % of full scale
The pulse and encoder inputs (terminals 18, 29, 32, 33) are galvanically isolated from the supply voltage
(PELV) and other high-voltage terminals.
1) Pulse inputs are 29 and 33
2) Encoder inputs: 18 = Z, 32 = A, and 33 = B
48