9.2.5 Analog Output - Terminal X30/8
Analog Output
Number of analog outputs
1
Terminal number
42
Current range at analog output
0–20 mA
Max. load GND - analog output
500 Ω
Accuracy on analog output
Max. error: 0.5% of full scale
Resolution on analog output
12 bit
9.3 Encoder Option MCB 102
The encoder module can be used as a feedback source for closed-loop flux control (
1-02 Flux Motor Feedback Source
), as well
as closed-loop speed control (
7-00 Speed PID Feedback Source
). Configure the encoder option in parameter group
17-**
Motor Feedback Option
.
The Encoder Option MCB 102 is used for
•
VVC
plus
closed-loop
•
Flux vector speed control
•
Flux vector torque control
•
Permanent magnet motor
Supported encoder types:
•
Incremental encoder: 5 V TTL type, RS422, maximum frequency: 410 kHz
•
Incremental encoder: 1Vpp, sine-cosine
•
Hiperface
®
Encoder: Absolute and Sine-Cosine (Stegmann/SICK)
•
EnDat encoder: Absolute and Sine-Cosine (Heidenhain) Supports version 2.1
•
SSI encoder: Absolute
NOTICE!
The LEDs are only visible when removing the LCP. Reaction in case of an encoder error can be selected in
17-61 Feedback Signal Monitoring
: None, Warning or Trip.
When the encoder option kit is ordered separately, the kit includes:
•
Encoder Option MCB 102
•
Enlarged LCP fixture and enlarged terminal cover
The encoder option does not support FC 302 adjustable frequency drives manufactured before week 50/2004.
Min. software version: 2.03 (
15-43 Software Version
)
Options and Accessories
Design Guide
252
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
MG34S222
9
9