9.2.2 Digital Inputs - Terminal X30/1-4
Digital Input
Number of digital inputs
4 (6)
Terminal number
18, 19, 27, 29, 32, 33
Logic
PNP or NPN
Voltage level
0–24 V DC
Voltage level, logic 0' PNP (GND=0 V)
<5 V DC
Voltage level, logic 1' PNP (GND=0 V)
>10 V DC
Voltage level, logic '0' NPN (GND=24 V)
<14 V DC
Voltage level, logic '1' NPN (GND=24 V)
>19 V DC
Maximum voltage on input
28 V continuous
Pulse frequency ranges
0–110 kHz
Duty cycle, min. pulse width
4.5 ms
Input impedance
>2 kΩ
9.2.3 Analog Inputs - Terminal X30/11, 12
Analog Input
Number of analog inputs
2
Terminal number
53, 54, X30.11, X30.12
Modes
Voltage
Voltage level
-10 V to +10 V
Input impedance
>10 kΩ
Max. voltage
20 V
Resolution for analog inputs
10 bit (+ sign)
Accuracy of analog inputs
Max. error 0.5% of full scale
Bandwidth
FC 302: 100 Hz
9.2.4 Digital Outputs - Terminal X30/6, 7
Digital Output
Number of digital outputs
2
Terminal number
X30.6, X30.7
Voltage level at digital/frequency output
0–24 V
Max. output current
40 mA
Max. load
≥ 600 Ω
Max. capacitive load
<10 nF
Minimum output frequency
0 Hz
Maximum output frequency
≤32 kHz
Accuracy of frequency output
Max. error: 0.1% of full scale