30-04 Wobble Jump Frequency [Hz]
Range:
Function:
voltage warning or trip (warning/alarm 7). This
parameter can only be changed in stop-mode
30-05 Wobble Jump Frequency [%]
Range:
Function:
0 %
*
[0 - 100 %] The jump frequency can also be expressed as
percentage of the center frequency. The
function is the same as for
.
30-06 Wobble Jump Time
Range:
Function:
Size related
*
[ 0.005 - 5.000 s]
30-07 Wobble Sequence Time
Range:
Function:
10.0 s
*
[1.0 - 1000.0 s] This parameter determines the wobble
sequence period. This parameter can
only be changed in stop-mode.
Wobble time = t
up
+ t
down
30-08 Wobble Up/ Down Time
Range:
Function:
5.0 s
*
[0.1 - 1000.0 s] Defines the individual up- and down
times for each wobble cycle.
30-09 Wobble Random Function
Option:
Function:
[0]
*
Off
[1]
On
30-10 Wobble Ratio
Range:
Function:
1.0
*
[0.1 - 10.0 ] If the ratio 0.1 is selected: t
down
is 10 times
greater than t
up
.
If the ratio 10 is selected: t
up
is 10 times
greater than t
down
.
30-11 Wobble Random Ratio Max.
Range:
Function:
10.0
*
[ par. 17-53 - 10.0 ] Enter the maximum allowed wobble
ratio.
30-12 Wobble Random Ratio Min.
Range:
Function:
0.1
*
[ 0.1 - par. 30-11 ] Enter the minimum allowed wobble
ratio.
30-19 Wobble Delta Freq. Scaled
Range:
Function:
0.0 Hz
*
[0.0 - 1000.0 Hz] Readout parameter. View the actual
wobble delta frequency after scaling
has been applied.
3.20.2 30-2* Adv. Start Adjust
30-20 High Starting Torque Time [s]
Range:
Function:
0.00 s
*
[0.00 - 60.00 s] High starting torque time for PM-Motor
in Flux mode without feedback. This
parameter is available for FC 302 only.
30-21 High Starting Torque Current [%]
Range:
Function:
100.0 %
*
[ 0.0 - 200.0 %] High starting torque current for PM-
Motor in Flux mode without
feedback. This parameter is available
for FC 302 only.
30-22 Locked Rotor Protection
Locked Rotor Protection for PM-Motor in Flux mode without
feedback. This parameter is available for FC 302 only.
Option:
Function:
[0]
*
Off
[1]
On
30-23 Locked Rotor Detection Time [s]
Locked Rotor Detection Time for PM-Motor in Flux mode without
feedback. This parameter is available for FC 302 only.
Range:
Function:
0.10 s
*
[0.05 - 1.00 s]
3.20.3 30-8* Compatibility
30-80 d-axis Inductance (Ld)
Range:
Function:
Size related
*
[ 0.000 -
1000.000 mH]
Enter the value of the d-axis
inductance. Obtain the value from
the permanent magnet motor
data sheet. The d-axis inductance
cannot be found by performing
an AMA.
30-81 Brake Resistor (ohm)
Range:
Function:
Size
related
*
[ 0.01 -
65535.00
Ohm]
Set the brake resistor value in
Ohms. This value is used for
monitoring the power to the brake
resistor in
. This parameter is only
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide