13-02 Stop Event
Select the boolean (TRUE or FALSE) input to activate Smart Logic
Control.
Option:
Function:
[90]
ATEX ETR cur. warning Selectable if
is set to [20] or [21]. If
the alarm 164 ATEX ETR
cur.lim.alarm is active, the output
will be 1.
[91]
ATEX ETR cur. alarm
Selectable if
is set to [20] or [21]. If
the alarm 166 ATEX ETR
freq.lim.alarm is active, the output
will be 1.
[92]
ATEX ETR freq. warning Selectable if
is set to [20] or [21] ]. If
the alarm 163 ATEX ETR
cur.lim.warning is active, the
output will be 1.
[93]
ATEX ETR freq. alarm
Selectable if
is set to [20] or [21]. If
the warning 165 ATEX ETR
freq.lim.warning is active, the
output will be 1.
[94]
RS Flipflop 0
[95]
RS Flipflop 1
[96]
RS Flipflop 2
[97]
RS Flipflop 3
[98]
RS Flipflop 4
[99]
RS Flipflop 5
[100] RS Flipflop 6
[101] RS Flipflop 7
13-03 Reset SLC
Option:
Function:
[0]
*
Do not reset
SLC
Retains programmed settings in all
parameter group 13 parameters (13-**).
[1]
Reset SLC
Resets all parameter group 13 parameters
(13-**) to default settings.
3.14.3 13-1* Comparators
Comparators are used for comparing continuous variables
(i.e. output frequency, output current, analog input etc.) to
fixed preset values.
Par. 13-11
Comparator Operator
=
TRUE longer than.
. . .
. . .
Par. 13-10
Comparator Operand
Par. 13-12
Comparator Value
130BB672.10
Illustration 3.50
In addition, there are digital values that will be compared
to fixed time values. See explanation in
13-10 Comparator
Operand
. Comparators are evaluated once in each scan
interval. Use the result (TRUE or FALSE) directly. All
parameters in this parameter group are array parameters
with index 0 to 5. Select index 0 to programme
Comparator 0, select index 1 to programme Comparator 1,
and so on.
13-10 Comparator Operand
Array [6]
Option:
Function:
Choice [1] to [31] are variables which
will be compared based on their values.
Choice [50] to [186] are digital values
(TRUE/FALSE) where the comparison is
based on the amount of time during
which they are set to TRUE or FALSE,
respectively. See
.
Select the variable to be monitored by
the comparator.
[0]
*
DISABLED
[0] DISABLED
The comparator is disabled.
[1]
Reference
[1] Reference
The resulting remote
reference (not local) as a percentage.
[2]
Feedback
[2] Feedback
In the unit [RPM] or [Hz]
[3]
Motor speed
[3] Motor speed
[RPM] or [Hz]
[4]
Motor current
[4] Motor current
[A]
[5]
Motor torque
[5] Motor torque
[Nm]
[6]
Motor power
[6] Motor power
[kW] or [hp]
[7]
Motor voltage
[7] Motor voltage
[V]
[8]
DC-link voltage
[8] DC-link voltage
[V]
[9]
Motor thermal
[9] Motor thermal
Expressed as a
percentage.
[10]
Drive thermal
[10] VLT thermal
Expressed as a
percentage.
[11]
Heat sink temp.
[11] Heat sink temp
Expressed as a
percentage.
[12]
Analog input
AI53
[12] Analog input AI53
Expressed as a
percentage.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
116
MG33ME02 - VLT
®
is a registered Danfoss trademark
3