7-06 Speed PID Lowpass Filter Time
Range:
Function:
example, if a time constant (τ) of 100 ms is
programmed, the cut-off frequency for the
low-pass filter will be 1/0.1= 10 RAD/sec.,
corresponding to (10/2 x π) = 1.6 Hz. The
PID regulator only regulates a feedback
signal that varies by a frequency of less than
1.6 Hz. If the feedback signal varies by a
higher frequency than 1.6 Hz, the PID
regulator does not react.
Practical settings of
taken from the number of pulses
per revolutions from encoder:
Encoder PPR
7-06 Speed PID
Lowpass Filter Time
512
10 ms
1024
5 ms
2048
2 ms
4096
1 ms
Table 3.21
Note that severe filtering can be detrimental
to dynamic performance.
This parameter is used with
[1] Speed closed loop
and
[2]
Torque
control.
The filter time in flux sensorless must be
adjusted to 3-5 ms.
0.6
0.6
f
g
= 10 Hz
175ZA293.11
Feedback
Disturbed feedback signal
t (Sec.)
t (Sec.)
Filtered feedback signal
Lowpass filter
Feedback
Illustration 3.45
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide