1.2
1.0
1.4
30
10
20
100
60
40
50
1.8
1.6
2.0
2000
500
200
400
300
1000
600
t [s]
e7
5z
a0
52
.1
3
I
M,N
(parameter 1-24)
I
M
f
OUT
= 2 x f
M,N
(parameter 1-23)
f
OUT
= 1 x f
M,N
f
OUT
= 0.2 x f
M,N
Illustration 38: ETR Profile
4.2.10.4 Klixon
The Klixon type thermal circuit breaker uses a KLIXON® metal dish. At a predetermined overload, the heat caused by the current
through the disc causes a trip.
Using a digital input and 24 V as supply:
Example: The drive trips when the motor temperature is too high.
Parameter setup:
Set
parameter 1-90 Motor Thermal Protection
to
[2] Thermistor Trip
.
Set
parameter 1-93 Thermistor Source
to
[6] Digital Input
.
PTC / Thermistor
OFF
ON
+
2
4
V
12 13 18
37
32
A
27
19
29
33
B
20
G
N
D
R
<6.6 k # >10.8 k #
e
3
0
b
a
1
5
1
.1
2
Illustration 39: Thermistor Connection
4.2.11 PM Settings
If
[2] Std. PM, non-salient
is selected in
parameter 1-10 Motor Construction
, enter the motor parameters manually in the following
order:
Parameter 1-24 Motor Current
.
Parameter 1-26 Motor Cont. Rated Torque
.
Parameter 1-25 Motor Nominal Speed
.
Parameter 1-39 Motor Poles
.
Parameter 1-30 Stator Resistance (Rs)
.
Parameter 1-37 d-axis Inductance (Ld)
.
Parameter 1-40 Back EMF at 1000 RPM
.
The following parameters have been added for PM motors.
Parameter 1-41 Motor Angle Offset
.
Parameter 1-07 Motor Angle Offset Adjust
.
Parameter 1-14 Damping Gain
.
AU373327181955en-000101 / 130R1208 | 95
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide