4.15 Parameter Group 15-** Drive Information
4.15.1 15-0* Operating Data
Parameter 15-00 Operating Hours
Table 521: Parameter 15-00 Operating Hours
15-00 Operating Hours
Default Value: 0 h
Parameter Type: Range, 0 - 2147483647 h
Setup: All set-ups
Conversion Index: 74
Data Type: Uint32
Change during operation: False
View for how many hours the drive has run. The value is saved when the drive is turned off.
Parameter 15-01 Running Hours
Table 522: Parameter 15-01 Running Hours
15-01 Running Hours
Default Value: 0 h
Parameter Type: Range, 0 - 2147483647 h
Setup: All set-ups
Conversion Index: 74
Data Type: Uint32
Change during operation: False
View how many hours the motor has run. Reset the counter in
parameter 15-07 Reset Running Hours Counter
. The value is saved
when the drive is turned off.
Parameter 15-02 kWh Counter
Table 523: Parameter 15-02 kWh Counter
15-02 kWh Counter
Default Value: 0 kWh
Parameter Type: Range, 0 - 2147483647 kWh
Setup: All set-ups
Conversion Index: 75
Data Type: Uint32
Change during operation: False
Register the power consumption of the motor as an average value over 1 hour. Reset the counter in
parameter 15-06 Reset kWh
Counter
.
Parameter 15-03 Power Up's
Table 524: Parameter 15-03 Power Up's
15-03 Power Up's
Default Value: 0
Parameter Type: Range, 0 - 2147483647
Setup: All set-ups
Conversion Index: 0
Data Type: Uint32
Change during operation: False
View the number of times the drive has been powered up.
Parameter 15-04 Over Temp's
Table 525: Parameter 15-04 Over Temp's
15-04 Over Temp's
Default Value: 0
Parameter Type: Range, 0 - 65535
Setup: All set-ups
Conversion Index: 0
Data Type: Uint16
Change during operation: False
View the number of drive temperature faults.