Enter the torque feed-forward factor value. The reference signal bypasses the torque controller by this value.
Parameter 7-19 Current Controller Rise Time
Table 382: Parameter 7-19 Current Controller Rise Time
7-19 Current Controller Rise Time
Default value: Size related
Parameter type: Range, 15 - 100%
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: True
Enter the value for the rise time of the current controller as a percentage of the control period.
4.8.5 7-2* Process Ctrl. Feedb.
Select the feedback sources for the process PID control,and how this feedback should be handled.
Parameter 7-20 Process CL Feedback 1 Resource
Table 383: Parameter 7-20 Process CL Feedback 1 Resource
7-20 Process CL Feedback 1 Resource
Default value: [0] No function
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
The effective feedback signal is made up of the sum of up to 2 different input signals. Select which drive input should be treated as
the source of the 1
st
of these signals. The 2
nd
input signal is defined in
parameter 7-22 Process CL Feedback 2 Resource
.
Option
Name
Description
[0]*
No function
[1]
Analog input 53
[2]
Analog input 54
[3]
Frerquency input 29
[4]
Frequency input 33
[7]
Analog input X30/11
[8]
Analog input X30/12
[15]
Analog input X48/2
[16]
Analog input X49/1
[17]
Analog input X49/3
[18]
Analog input X49/5
Parameter 7-22 Process CL Feedback 2 Resource
Table 384: Parameter 7-22 Process CL Feedback 2 Resource
7-22 Process CL Feedback 2 Resource
Default value: [0] No function
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
The effective feedback signal is made up of the sum of up to 2 different input signals. Select which drive input should be treated as
the source of the 2
nd
of these signals. The 1
st
input signal is defined in
parameter 7-20 Process CL Feedback 1 Resource
.
AU373327181955en-000101 / 130R1208