Parameter 5-26 Terminal X46/13 Digital Input
Table 307: Parameter 5-26 Terminal X46/13 Digital Input
5-26 Terminal X46/13 Digital Input
Default value: [0] No operation
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
The options for this parameter are the same as those listed for
parameter 5-20 Terminal X46/1 Digital Input
.
4.6.3 5-3* Digital Outputs
The 2 solid-state digital outputs are common for terminals 27 and 29. Set the I/O function for terminal 27 in
parameter 5-01 Terminal
27 Mode
, and set the I/O function for terminal 29 in
parameter 5-02 Terminal 29 Mode
.
N O T I C E
These parameters cannot be adjusted while the motor is running.
Table 308: Digital Outputs, Function Descriptions - 1
Option
Function
[0]
No operation
Default for all digital outputs and relay outputs.
[1]
Control ready
The control card is ready.
[2]
Drive ready
The drive is ready for operation and applies a supply signal on the control card.
[3]
Drive rdy/rem ctrl
The drive is ready for operation and is in auto-on mode.
[4]
Enable/no warning
Ready for operation. No start or stop command has been given (start/disable). No warnings are
active.
[5]
Running
The motor runs, and shaft torque is present.
[6]
Running/no warning
The output speed is higher than the speed set in
parameter 1-81 Min Speed for Function at Stop
[RPM]
. The motor runs and there are no warnings.
[7]
Run inrange/no warn The motor runs within the programmed current and speed ranges set in
parameter 4-50 Warning
Current Low
to
parameter 4-53 Warning Speed High
. There are no warnings.
[8]
Run on ref/no warn
The motor runs at reference speed. There are no warnings.
[9]
Alarm
An alarm activates the output. There are no warnings.
[10]
Alarm or warning
An alarm or warning activates the output.
[11]
At torque limit
The torque limit set in
parameter 4-16 Torque Limit Motor Mode
or
parameter 4-17 Torque Limit
Generator Mode
has been exceeded.
[12]
Out of current range
The motor current is outside the range set in
parameter 4-18 Current Limit
.
[13]
Below current, low
The motor current is lower than set in
parameter 4-50 Warning Curent Low
.
[14]
Above current, high
The motor current is higher than set in
parameter 4-51 Warning Current High
.
[15]
Out of speed range
The output frequency is outside the frequency range set in
parameter 4-52 Warning Speed Low
and
parameter 4-53 Warning Speed High
.
[16]
Below speed, low
Output speed is lower than the setting in
parameter 4-52 Warning Speed Low
.
[17]
Above speed, high
The output speed is higher than the setting in
parameter 4-53 Warning Speed High
.
AU373327181955en-000101 / 130R1208 | 157
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide