Option Name Description
The drive does not issue a missing motor phase alarm.
[1]
On
Before each start, the drive checks if all 3 motor phases are present. The check is performed without any shaft
movement. The function also enables 3-phase detection in U/f and VVC
+
mode. See description in
parameter
4-58 Missing Motor Phase Function
.
The table details the motor check at start for different motor modes.
Table 262: Motor Check at Start for Different Motor Types
Option Motor Check
at Start
U/f
VVC
+
Flux
open
loop
Flux
closed
loop
[0]
Off
No function.
[1]
On
(1)
Check for missing motor phase before start is executed or enables
3-phase detection for U/f and VVC
+
in
parameter 4-58 Missing Motor
Phase Function
.
1
When the motor check is done at start and a missing motor phase is detected, the motor starts at trip 10 ms. This means that
parameter 4-58
Missing Motor Phase Function
is set to
[1] Trip 100 ms
.
When
parameter 4-59 Motor Check At Start
is set to
[1] On
, do not set
parameter 4-58 Missing Motor Phase Function
to the following
options:
[0] Disabled
[5] Motor check
4.5.6 4-6* Speed Bypass
Some systems require that certain output frequencies or speeds are avoided due to resonance problems in the system. A maximum
of 4 frequency or speed ranges can be avoided.
Parameter 4-60 Bypass Speed From [RPM]
Table 263: Parameter 4-60 Bypass Speed From [RPM]
4-60 Bypass Speed From [RPM]
Default value: Size related
Parameter type: Range, 0 - par. 4-13 RPM, Array [4]
Setup: All setups
Conversion index: 67
Data type: Uint16
Change during operation: True
Some systems call for avoiding certain output speeds due to resonance problems in the system. Enter the lower limits of the speeds
to be avoided.
Parameter 4-61 Bypass Speed From [Hz]
Table 264: Parameter 4-61 Bypass Speed From [Hz]
4-61 Bypass Speed From [Hz]
Default value: Size related
Parameter type: Range, 0 - par. 4-14 Hz, Array [4]
Setup: All setups
Conversion index: -1
Data type: Uint16
Change during operation: True
Some systems require that certain output frequencies or speeds are avoided due to resonance problems in the system. Enter the
lower limits of the speeds to be avoided.