4.1.24 29-** Water Application Functions
Param-
eter #
Parameter description
Default value
4 set-up
Change during
operation
Conversion
index
Type
29-0* Pipe Fill
29-00
Pipe Fill Enable
[0] Disabled
2 set-ups
FALSE
-
Uint8
29-01
Pipe Fill Speed [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
29-02
Pipe Fill Speed [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
29-03
Pipe Fill Time
0 s
All set-ups
TRUE
-2
Uint32
29-04
Pipe Fill Rate
0.001
ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
29-05
Filled Setpoint
0 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
29-06
No-Flow Disable Timer
0 s
All set-ups
TRUE
-2
Uint32
29-07
Filled setpoint delay
0 s
All set-ups
TRUE
-1
Uint16
29-1* Deragging Function
29-10
Derag Cycles
ExpressionLimit
2 set-ups
FALSE
0
Uint32
29-11
Derag at Start/Stop
[0] Off
1 set-up
TRUE
-
Uint8
29-12
Deragging Run Time
0 s
All set-ups
TRUE
0
Uint16
29-13
Derag Speed [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
29-14
Derag Speed [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
29-15
Derag Off Delay
10 s
All set-ups
TRUE
0
Uint16
29-2* Derag Power Tuning
29-20
Derag Power[kW]
0 kW
All set-ups
TRUE
1
Uint32
29-21
Derag Power[HP]
0 hp
All set-ups
TRUE
-2
Uint32
29-22
Derag Power Factor
200%
All set-ups
TRUE
0
Uint16
29-23
Derag Power Delay
601 s
All set-ups
TRUE
0
Uint16
29-24
Low Speed [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
29-25
Low Speed [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
29-26
Low Speed Power [kW]
ExpressionLimit
All set-ups
TRUE
1
Uint32
29-27
Low Speed Power [HP]
ExpressionLimit
All set-ups
TRUE
-2
Uint32
29-28
High Speed [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
29-29
High Speed [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
29-30
High Speed Power [kW]
ExpressionLimit
All set-ups
TRUE
1
Uint32
29-31
High Speed Power [HP]
ExpressionLimit
All set-ups
TRUE
-2
Uint32
29-32
Derag On Ref Bandwidth
5%
All set-ups
TRUE
0
Uint8
29-33
Power Derag Limit
3 N/A
2 set-ups
FALSE
0
Uint8
29-34
Consecutive Derag Interval
ExpressionLimit
All set-ups
FALSE
0
Uint16
29-35
Derag at Locked Rotor
[0] Disabled
All set-ups
TRUE
-
Uint8
29-4* Pre/Post Lube
29-40
Pre/Post Lube Function
[0] Disabled
All set-ups
TRUE
-
Uint8
29-41
Pre Lube Time
10 s
All set-ups
TRUE
0
Uint16
29-42
Post Lube Time
10 s
All set-ups
TRUE
0
Uint16
29-5* Flow Confirmation
29-50
Validation Time
ExpressionLimit
All set-ups
TRUE
-2
Uint32
29-51
Verification Time
15 s
All set-ups
TRUE
-2
Uint32
29-52
Signal Lost Verification Time
1 s
All set-ups
TRUE
-2
Uint32
29-53
Flow Confirmation Mode
[0] Confirmation
Only
All set-ups
FALSE
-
Uint8
29-6* Flow Meter
29-60
Flow Meter Monitor
[0] Disabled
All set-ups
TRUE
-
Uint8
29-61
Flow Meter Source
[0] Analog Input 53
All set-ups
TRUE
-
Uint8
29-62
Flow Meter Unit
[0] l/s
All set-ups
TRUE
-
Uint8
29-63
Totalized Volume Unit
[0] Disabled
All set-ups
TRUE
-
Uint8
29-64
Actual Volume Unit
[0] Disabled
All set-ups
TRUE
-
Uint8
Parameter Lists
Programming Guide
MG20OB02
Danfoss A/S © 05/2018 All rights reserved.
279
4
4