5 Electrical Installation
5.1 Safety Instructions
See the
Safety Precautions
section for general safety warnings.
NOTICE
EXCESSIVE HEAT AND PROPERTY DAMAGE
Overcurrent can generate excessive heat within the drive. Failure to provide overcurrent protection can result in risk of fire and
property damage.
-
Additional protective equipment such as shortcircuit protection or motor thermal protection between drive and motor is
required for applications with multiple motors.
-
Input fusing is required to provide short circuit and overcurrent protection. If fuses are not factory-supplied, the installer
must provide them. See maximum fuse ratings in the
Specifications
chapter.
NOTICE
WIRE TYPE AND RATINGS
All wiring must comply with local and national regulations regarding cross-section and ambient temperature requirements. For
power connections, minimum 75 °C (167 °F) rated copper wire is recommended. Refer to the the
Specifications
chapter.
WARNING
INDUCED VOLTAGE
Induced voltage from output motor cables from different drives that are run together can charge equipment capacitors even
with the equipment turned off and locked out. Failure to run output motor cables separately or use shielded cables could result
in death or serious injury.
-
Run output motor cables separately or use shielded cables.
-
Simultaneously lock out all the drives.
WARNING
SHOCK HAZARD
The drive can cause a DC current in the PE conductor. Failure to use a Type B residual current-operated protective device (RCD)
may lead to the RCD not providing the intended protection and therefore may result in death or serious injury.
-
When an RCD is used for protection against electrical shock, only a Type B device is allowed on the supply side.
NOTICE
PROPERTY DAMAGE
Protection against motor overload is not included in the default setting. For the North American market, the ETR function
provides class 20 motor overload protection in accordance with NEC. Failure to set the ETR function means that motor overload
protection is not provided and property damage can occur if the motor overheats.
-
Enable the ETR function by setting
parameter 1-90 Motor Thermal Protection
to
[ETR trip]
or
[ETR warning]
.
Electrical Installation
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708| 35
Danfoss A/S © 2020.01
Summary of Contents for VLT AQUA Drive FC 202
Page 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Page 2: ......
Page 3: ......
Page 4: ......
Page 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Page 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...