Troubleshooting
•
Increase the ambient temperature of the unit.
•
Supply a trickle amount of current to the drive whenever the motor is stopped by setting
parameter 2-00 DC Hold/Preheat Current
to
5% and
parameter 1-80 Function at Stop
.
8.4.63 ALARM 67, Option Module Configuration has Changed
Cause
One or more options have either been added or removed since the last power-down.
Troubleshooting
•
Check that the configuration change is intentional and reset the unit.
8.4.64 ALARM 68, Safe Stop Activated
Cause
Safe Torque Off (STO) has been activated.
Troubleshooting
•
To resume normal operation, apply 24 V DC to terminal 37, then send a reset signal (via bus, digital, or by pressing [Reset]).
8.4.65 ALARM 69, Power Card Temperature
Cause
The temperature sensor on the power card is either too hot or too cold.
Troubleshooting
•
Check that the ambient operating temperature is within the limits.
•
Check for clogged filters.
•
Check fan operation.
•
Check the power card.
8.4.66 ALARM 70, Illegal FC Configuration
Cause
The control card and power card are incompatible.
Troubleshooting
•
To check compatibility, contact the Danfoss supplier with the type code from the unit nameplate and the part numbers on the
cards.
Maintenance, Diagnostics, and
Troubleshooting
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
120 | Danfoss A/S © 2020.01
Summary of Contents for VLT AQUA Drive FC 202
Page 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Page 2: ......
Page 3: ......
Page 4: ......
Page 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Page 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...