![Danfoss VLT AQUA Drive FC 202 Instruction Manual Download Page 55](http://html1.mh-extra.com/html/danfoss/vlt-aqua-drive-fc-202/vlt-aqua-drive-fc-202_instruction-manual_3505209055.webp)
8.1.2 Line Power Supply 3x200–240 V AC
Type Designation
PK25
PK37
PK55
PK75
P1K1
P1K5
P2K2
P3K0
P3K7
Typical Shaft Output [kW]
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3.0
3.7
Typical Shaft Output [HP] at 208 V
0.25
0.37
0.55
0.75
1.5
2.0
2.9
4.0
4.9
IP20/Chassis
6)
A2
A2
A2
A2
A2
A2
A2
A3
A3
IP21/Type 1
A2
A2
A2
A2
A2
A2
A2
A3
A3
IP55/Type 12
A5
A5
A5
A5
A5
A5
A5
A5
A5
IP66/NEMA 4X
A5
A5
A5
A5
A5
A5
A5
A5
A5
Output current
Continuous (3x200–240 V) [A]
1.8
2.4
3.5
4.6
6.6
7.5
10.6
12.5
16.7
Intermittent (3x200–240 V) [A]
1.98
2.64
3.85
5.06
7.26
8.3
11.7
13.8
18.4
Continuous kVA (208 V AC) [kVA]
0.65
0.86
1.26
1.66
2.38
2.70
3.82
4.50
6.00
Max. input current
Continuous (3x200–240 V) [A]
1.6
2.2
3.2
4.1
5.9
6.8
9.5
11.3
15.0
Intermittent (3x200–240 V) [A]
1.7
2.42
3.52
4.51
6.5
7.5
10.5
12.4
16.5
Max. pre-fuses
1)
[A]
10
10
10
10
20
20
20
32
32
Additional Specifications
Estimated power loss at rated max. load [W]
4)
21
29
42
54
63
82
116
155
185
Max. cable size (line power, motor, brake) [mm
2
/
(AWG)]
2)
[0.2–4]/(4–10)
Efficiency
3)
0.94
0.94
0.95
0.95
0.96
0.96
0.96
0.96
0.96
Table 8.2 Line Power Supply 3x200–240 V AC - Normal overload 110% for 1 minute, PK25-P3K7