8 Specifications
8.1 Power-Dependent Specifications
8.1.1 Mains Supply 3x380–480 V AC
Mains supply 3x380–480 V AC
N160
N200
N250
High/normal load*
HO
NO
HO
NO
HO
NO
Typical shaft output at 400 V [kW]
132
160
160
200
200
250
Typical shaft output at 460 V [HP]
200
250
250
300
300
350
Typical shaft output at 480 V [kW]
160
200
200
250
250
315
Enclosure protection rating IP21
D1n
D2n
D2n
Enclosure protection rating IP54
D1n
D2n
D2n
Output current
130BA230.10
Continuous (at 400 V) [A]
260
315
315
395
395
480
Intermittent (60 s overload) (at 400
V) [A]
390
347
473
435
593
528
Continuous (at 460/480 V) [A]
240
302
302
361
361
443
Intermittent (60 s overload) (at
460/480 V) [A]
360
332
453
397
542
487
Continuous KVA (at 400 V) [KVA]
180
218
218
274
274
333
Continuous KVA (at 460 V) [KVA]
191
241
241
288
288
353
Continuous KVA (at 480 V) [KVA]
208
262
262
313
313
384
Maximum input current
130BA229.10
Continuous (at 400 V ) [A]
251
304
304
381
381
463
Continuous (at 460/480 V) [A]
231
291
291
348
348
427
Maximum cable size, mains motor,
brake, and load share [mm
2
(AWG
2)
)]
Motor, brake and load
share: 2x95 (2x3/0)
Mains: 2x185 (2x350)
2x185
(2x350 mcm)
2x185
(2x350 mcm)
Maximum external mains fuses [A]
1
400
550
630
Total LHD loss 400 V AC [kW]
7428
8725
8048
9831
9753
11371
Total back channel loss 400 V AC
[kW]
6302
7554
6877
8580
8503
10020
Total filter loss 400 V AC [kW]
4505
4954
4954
5714
5714
6234
Total LHD loss 460 V AC [kW]
7490
8906
7875
9046
8937
10626
Total back channel loss 460 V AC
[kW]
5974
7343
6274
7374
7338
8948
Total filter loss 460 V AC [kW]
3604
4063
3751
4187
4146
4822
Weight, enclosure protection
rating IP21, IP54 [kg]
352
413
413
Efficiency
4)
0.96
Acoustic noise
85 dBa
Output frequency
0–590 Hz
Heat sink overtemperature trip
105 °C
105 °C
105 °C
Power card ambient trip
85 °C
* High overload = 150% current for 60 s, normal overload = 110% current for 60 s.
Table 8.1 D-frame Ratings
Specifications
VLT
®
AQUA Drive FC 202 Low Harmonic Drive
82
Danfoss A/S © 10/2015 All rights reserved.
MG21B322