Type designation
P37K
P45K
P55K
P75K
(1)
P90K/N90K
(1)
Intermittent (60 s overload) (3x525–
550 V) [A]
54
47.3 64.5 59.4 81
71.5
97.5
95.7
130.5 115.5
Continuous (3x551–690 V) [A]
34
41
41
52
52
62
62
83
83
100
Intermittent (60 s) (3x551–690 V) [A]
51
45.1 61.5 57.2 78
68.2
93
91.3
124.5 110
Continuous kVA at 550 V [kVA]
34.3 41
41
51.4 51.4 61.9
61.9
82.9
82.9
100
Continuous kVA at 690 V [kVA]
40.6 49
49
62.1 62.1 74.1
74.1
99.2
99.2
119.5
Maximum input current
Continuous 550 V [A]
36
49
49
59
59
71
71
87
87
99
Intermittent (60 s overload) (3x525–
550 V) [A]
54
53.9 72
64.9 87
78.1
105
95.7
129
108.9
Continuous (3x551–690 V) [A]
36
48
48
58
58
70
70
86
–
–
Intermittent (3x551–690 V) [A]
54
52.8 72
63.8 87
77
105
94.6
–
–
Additional specifications
Maximum cable cross–section for mains
and motor [mm
2
(AWG)]
150 (300 MCM)
Maximum cable cross–section for brake
and load sharing [mm
2
(AWG)]
95 (3/0)
Maximum cable cross–section
(3)
for
mains disconnect [mm
2
(AWG)]
95 (3/0)
185, 150, 120 (350 MCM,
300 MCM, 4/0)
–
Estimated power loss
(4)
at rated maxi-
mum load [W]
(5)
600
740
740
900
900
1100 1100
1500
1500
1800
Efficiency
(6)
0.98
1
Enclosure sizes for N75K, N90K are D3h for IP20/Chassis, and D5h for IP54/Type 12.
2
High overload=150% or 160% torque for a duration of 60 s. Normal overload=110% torque for a duration of 60 s.
3
The 3 values for the maximum cable cross-section are for single core, flexible wire, and flexible wire with sleeve, respectively.
4
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to
mydrive ecosmart on
. For efficiency class see
5
Efficiency measured at nominal current. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to mydrive ecos-
mart on
6
Measured using 5 m (16 ft) shielded motor cables at rated load and rated frequency. For more detailed efficiency values and part load losses ac-
cording IEC/EN 61800-9-2 refer to mydrive ecosmart on
8.2 Mains Supply
Supply terminals
L1, L2, L3
Supply voltage
(1)(2)
200–240 V ±10%
Supply voltage
(1)(2)
380–480 V/500–600 V ±10%
Supply voltage
(1)(2)
525–600 V ±10%
Supply frequency
(3)
47.5–63 Hz
Maximum imbalance temporary between mains phases
3.0% of rated supply voltage
True power factor (λ)
≥0.9 nominal at rated load
AJ300847815559en-000101 / 130R0337 | 89
Danfoss A/S © 2020.09
Specifications
VLT® AQUA Drive FC 202
Design Guide