Type designation
P1K1
P1K5
P2K2
P3K0
P3K7
P5K5
P7K5
P15K
P22K
Efficiency
(5)
0.98
1
Two wires are required.
2
Variant not available in IP21.
3
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to
mydrive ecosmart on
. For efficiency class see
.
4
Efficiency measured at nominal current. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to mydrive ecos-
mart on
. For efficiency class see
.
5
Measured using 5 m (16 ft) shielded motor cables at rated load and rated frequency. For more detailed efficiency values and part load losses ac-
cording IEC/EN 61800-9-2 refer to mydrive ecosmart on
. For efficiency class see
.
8.1.2 Mains Supply 3x200–240 V AC
Table 26: Mains Supply 3x200–240 V AC, PK25–PK75
Type designation
PK25
PK37
PK55
PK75
High/normal overload
(1)
HO NO HO NO HO NO HO NO
Typical shaft output [kW]
0.25
0.37
0.55
0.75
Typical shaft output at 208 V [hp]
0.34
0.50
0.75
1.0
Protection rating IP20/Chassis
(2)
A2
A2
A2
A2
Protection rating IP21/Type 1
A2
A2
A2
A2
Protection rating IP55/Type 12
Protection rating IP66/NEMA 4X
A4/A5
A4/A5
A4/A5
A4/A5
Output current
Continuous (3x200–240 V) [A]
1.8
2.4
3.5
4.6
Intermittent (3x200–240 V) [A]
2.7 2.0 3.6 2.6 5.3 3.9 6.9 5.1
Continuous kVA at 208 V [kVA]
0.65
0.86
1.26
1.66
Maximum input current
Continuous (3x200–240 V) [A]
1.6
2.2
3.2
4.1
Intermittent (3x200–240 V) [A]
2.4 1.8 3.3 2.4 4.8 3.5 6.2 4.5
Maximum pre-fuses [A]
10
10
10
10
Additional specifications
Maximum cable cross-section
(3)
for mains, motor, brake, and load sharing [mm
2
(AWG)]
4, 4, 4 (12, 12, 12)
(minimum 0.2 (24))
Maximum cable cross-section
(3)
for mains disconnect [mm
2
(AWG)]
6, 4, 4 (10, 12, 12)
Estimated power loss
(4)
at rated maximum load [W]
(5)
21
29
42
54
AJ300847815559en-000101 / 130R0337
72 | Danfoss A/S © 2020.09
Specifications
VLT® AQUA Drive FC 202
Design Guide