FC 202
Horizontal braking 10% duty cycle
T2
3.0
(4.0)
45
53.7
48
0.200
175U3031 –
–
–
1.5 (16)
1.9
T2
3.7
(5.0)
31.5
39.9
35
0.300
175U3325 –
–
–
1.5 (16)
2.7
T2
5.5
(7.5)
22.5
28.7
27
0.360
175U3326 175U3477
175U3478
–
1.5 (16)
3.5
T2
7.5 (10) 17.7
20.8
18
0.570
175U3327 175U3442
175U3441
–
1.5 (16)
5.3
T2
11 (15)
12.6
14
13
0.680
175U3328 175U3059
175U3060
–
1.5 (16)
6.8
T2
15 (20)
8.7
10.2
9.0
1.130
175U3329 175U3068
175U3069
–
2.5 (14)
10.5
T2
18.5
(25)
5.3
8.2
5.7
1.400
175U3330 175U3073
175U3074
–
4 (12)
15
T2
22 (30)
5.1
6.9
5.7
1.700
175U3331 175U3483
175U3484
–
4 (12)
16
T2
30 (40)
3.2
5.0
3.5
2.200
175U3332 175U3080
175U3081
–
6 (10)
24
T2
37 (50)
3.0
4.1
3.5
2.800
175U3333 175U3448
175U3447
–
10 (8)
27
T2
45 (60)
2.4
3.3
2.8
3.200
175U3334 175U3086
175U3087
–
16 (6)
32
13.2.9.2 Order Numbers for Brake Resistors, T2, Vertical Braking 40% Duty Cycle
Table 134: Order Numbers for Brake Resistors, T2, Vertical Braking 40% Duty Cycle
FC 202
Vertical braking 40% duty cycle
Drive data
Brake resistor data
Installation
Danfoss part numbers
Mains
type
P
m
[kW]
R
min
[Ω]
R
br.nom
[Ω]
R
rec
[Ω]
P
br.cont
[kW]
Wire IP54
Screw ter-
minal IP65
Screw ter-
minal IP20
Bolt con-
nection
IP20
Cable
cross-
section
[mm
2
(AWG)]
Ther-
mo
relay
[A]
T2
0.25
(0.34)
380
691.3
630
0.100
175U3002 –
–
–
1.5 (16)
0.4
T2
0.37
(0.50)
380
466.7
410
0.100
175U3004 –
–
–
1.5 (16)
0.5
T2
0.55
(0.75)
275
313.7
300
0.200
175U3096 –
–
–
1.5 (16)
0.8
T2
0.75
(1.0)
188
230
200
0.200
175U3008 –
–
–
1.5 (16)
0.9
T2
1.1
(1.5)
130
152.9
145
0.300
175U3300 –
–
–
1.5 (16)
1.3
T2
1.5
(2.0)
81
110.5
100
0.450
175U3301 175U3402
175U3401
–
1.5 (16)
2.0
T2
2.2
(3.0)
58.5
74.1
70
0.570
175U3302 175U3404
175U3403
–
1.5 (16)
2.7
AJ300847815559en-000101 / 130R0337
186 | Danfoss A/S © 2020.09
How to Order a Drive
VLT® AQUA Drive FC 202