12.1.9 Wiring Configuration: Motor Thermistor
Table 120: Motor Thermistor
Parameters
e3
0b
b6
86
.1
3
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
A53
U - I
D IN
37
Drive
Function
Setting
Parameter 1-90 Motor Thermal Protection
[2] Thermistor trip
Parameter 1-93 Thermistor Source
[1] Analog input 53
* = Default value
If only a warning is required, set
parameter 1-90 Motor Thermal Protection
to
[1] Thermistor warn-
ing
.
D IN 37 is an option.
AJ300847815559en-000101 / 130R0337
176 | Danfoss A/S © 2020.09
Basic I/O Configurations
VLT® AQUA Drive FC 202
Design Guide