Illustration 57: Derating of Output Current versus Altitude at T
AMB,MAX
for Enclosure Sizes A, B, and C
Max.I
out
(%)
at T
AMB, MAX
Altitude (km)
HO
NO
T
at 100% I
out
100%
96%
92%
0 K
-3 K
-6 K
1 km
2 km
3 km
-5 K
-8 K
-11 K
e3
0b
t8
66
.1
0
AMB, MAX
Illustration 58: Derating of Output Current Based on Altitude at T
AMB,MAX
At altitudes above 2000 m (6561 ft), contact Danfoss regarding PELV.
Alternatively, lower the ambient temperature at high altitudes and thereby ensure 100% output current at high altitudes. As an ex-
ample of how to read the graph, the situation at 2000 m (6561 ft) is elaborated for an enclosure size B with T
AMB,MAX
= 50 °C (122 °F).
Either the output current has to be reduces to 91% at T
AMB,MAX
, or the maximum temperature has to be reduced by 3.3 K at 100%
I
out
. This means that 100% of the rated output current is available at 41.7 °C (107 °F) continuous and 46.7 °C (116 °F) intermittent.