26-00 Terminal X42/1 Mode
Option:
Function:
Terminal X42/1 can be programmed as an analog input accepting a voltage or input from either
Pt1000 (1000
Ω
at 0
°
C) or Ni 1000 (1000
Ω
at 0
°
C) temperature sensors. Select the desired mode.
Pt 1000
, [2] and
Ni 1000
[4] if operating in Celsius - Pt 1000 [3] and Ni 1000 [5] if operating in
Fahrenheit.
Notice: If the input is not in use, it must be set for Voltage!
If set for temperature and used as feed back, the unit must be set for either Celsius or Fahrenheit
(par. 20-12
Reference/Feedback Unit
or par.21-50
[1] *
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
26-01 Terminal X42/3 Mode
Option:
Function:
Terminal X42/3 can be programmed as an analog input accepting a voltage or input from either Pt
1000 or Ni 1000 temperature sensors. Select the desired mode.
Pt 1000, [2] and Ni 1000, [4] if operating in Celsius - Pt 1000, [3] and Ni 1000, [5] if operating in
Fahrenheit.
Notice: If the input is not in use, it must be set for Voltage!
If set for temperature and used as feed back, the unit must be set for either Celsius or Fahrenheit
(par. 20-12
Reference/Feedback Unit
or par.21-50
[1] *
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
26-02 Terminal X42/5 Mode
Option:
Function:
Terminal X42/5 can be programmed as an analog input accepting a voltage or input from either Pt
1000 (1000
Ω
at 0
°
C) or Ni 1000 (1000
Ω
at 0
°
C) temperature sensors. Select the desired mode.
Pt 1000, [2] and Ni 1000, [4] if operating in Celsius - Pt 1000, [3] and Ni 1000, [5] if operating in
Fahrenheit.
Notice: If the input is not in use, it must be set for Voltage!
If set for temperature and used as feed back, the unit must be set for either Celsius or Fahrenheit
(par. 20-12
Reference/Feedback Unit
or par.21-50
[1] *
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
26-10 Terminal X42/1 Low Voltage
Range:
Function:
0.07 V*
[0.00 - par. 6-31 V]
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
feedback value set in par.26-14
Term. X42/1 Low Ref./Feedb. Value
VLT
®
AQUA Drive Programming Guide
2 Parameter Description
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark
227