23-02 OFF Time
Array [10]
Range:
Function:
0 N/A
*
[0 - 0
N/A]
Sets the OFF time for the timed action.
NOTE!
The adjustable frequency drive has no
backup of the clock function and the set
date/time will reset to default
(2000-01-01 00:00) after a power-down
unless the Analog I/O option module
(OPCAIO) with battery backup of the Real
Time Clock is installed. In
0-79 Clock Fault
,
it is possible to program for a warning in
case the clock has not been set properly,
e.g., after a power-down.
23-03 OFF Action
Array [10]
Option:
Function:
Select the action during OFF Time.
See
13-52 SL Controller Action
for
descriptions of the options.
[0]
*
DISABLED
[1]
No action
[2]
Select set-up 1
[3]
Select set-up 2
[4]
Select set-up 3
[5]
Select set-up 4
[10] Select preset ref 0
[11] Select preset ref 1
[12] Select preset ref 2
[13] Select preset ref 3
[14] Select preset ref 4
[15] Select preset ref 5
[16] Select preset ref 6
[17] Select preset ref 7
[18] Select ramp 1
[19] Select ramp 2
[22] Run
[23] Run reverse
[24] Stop
[26] Dcstop
[27] Coast
[28] Freeze output
[29] Start timer 0
[30] Start timer 1
[31] Start timer 2
[32] Set digital out A low
[33] Set digital out B low
[34] Set digital out C low
23-03 OFF Action
Array [10]
Option:
Function:
[35] Set digital out D low
[36] Set digital out E low
[37] Set digital out F low
[38] Set digital out A high
[39] Set digital out B high
[40] Set digital out C high
[41] Set digital out D high
[42] Set digital out E high
[43] Set digital out F high
[60] Reset Counter A
[61] Reset Counter B
[70] Start Timer 3
[71] Start Timer 4
[72] Start Timer 5
[73] Start Timer 6
[74] Start Timer 7
23-04 Occurrence
Array [10]
Option:
Function:
Select the day(s) to which the timed
action applies. Specify working/non-
working days in
0-81 Working Days
,
0-82 Additional Working Days
and
0-83 Additional Non-Working Days
.
[0]
*
All days
[1]
Working days
[2]
Non-working days
[3]
Monday
[4]
Tuesday
[5]
Wednesday
[6]
Thursday
[7]
Friday
[8]
Saturday
[9]
Sunday
6.2.10 Water Application Functions, 29-**
The group contains parameters used for monitoring water/
wastewater applications.
29-00 Pipe Fill Enable
Option:
Function:
29-01 Pipe Fill Speed [RPM]
Range:
Function:
Size related
*
[par. 4-11 - par. 4-13 RPM]
How to program the adjustab...