6.3.8 Analog In/Out 6-**
Par. No.
#
Parameter description
Default value
4 set-up
Change during
operation
Conver-
sion index
Type
6-0* Analog I/O Mode
6-00
Live Zero Timeout Time
10 s
All set-ups
TRUE
0
Uint8
6-01
Live Zero Timeout Function
[0] Off
All set-ups
TRUE
-
Uint8
6-1* Analog Input 53
6-10
Terminal 53 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
6-11
Terminal 53 High Voltage
10.00 V
All set-ups
TRUE
-2
Int16
6-12
Terminal 53 Low Current
4.00 mA
All set-ups
TRUE
-5
Int16
6-13
Terminal 53 High Current
20.00 mA
All set-ups
TRUE
-5
Int16
6-14
Terminal 53 Low Ref./Feedb. Value
0.000 N/A
All set-ups
TRUE
-3
Int32
6-15
Terminal 53 High Ref./Feedb.
Value
ExpressionLimit
All set-ups
TRUE
-3
Int32
6-16
Terminal 53 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
6-17
Terminal 53 Live Zero
[1] Enabled
All set-ups
TRUE
-
Uint8
6-2* Analog Input 54
6-20
Terminal 54 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
6-21
Terminal 54 High Voltage
10.00 V
All set-ups
TRUE
-2
Int16
6-22
Terminal 54 Low Current
4.00 mA
All set-ups
TRUE
-5
Int16
6-23
Terminal 54 High Current
20.00 mA
All set-ups
TRUE
-5
Int16
6-24
Terminal 54 Low Ref./Feedb. Value
0.000 N/A
All set-ups
TRUE
-3
Int32
6-25
Terminal 54 High Ref./Feedb.
Value
100.000 N/A
All set-ups
TRUE
-3
Int32
6-26
Terminal 54 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
6-27
Terminal 54 Live Zero
[1] Enabled
All set-ups
TRUE
-
Uint8
6-3* Analog Input X30/11
6-30
Terminal X30/11 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
6-31
Terminal X30/11 High Voltage
10.00 V
All set-ups
TRUE
-2
Int16
6-34
Term. X30/11 Low Ref./Feedb.
Value
0.000 N/A
All set-ups
TRUE
-3
Int32
6-35
Term. X30/11 High Ref./Feedb.
Value
100.000 N/A
All set-ups
TRUE
-3
Int32
6-36
Term. X30/11 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
6-37
Term. X30/11 Live Zero
[1] Enabled
All set-ups
TRUE
-
Uint8
6-4* Analog Input X30/12
6-40
Terminal X30/12 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
6-41
Terminal X30/12 High Voltage
10.00 V
All set-ups
TRUE
-2
Int16
6-44
Term. X30/12 Low Ref./Feedb.
Value
0.000 N/A
All set-ups
TRUE
-3
Int32
6-45
Term. X30/12 High Ref./Feedb.
Value
100.000 N/A
All set-ups
TRUE
-3
Int32
6-46
Term. X30/12 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
6-47
Term. X30/12 Live Zero
[1] Enabled
All set-ups
TRUE
-
Uint8
How to program the adjustab...
VLT AQUA 12-Pulse High Power Instruction Manual
6-44
MG.20.Y1.22 - VLT
®
is a registered Danfoss trademark
6
6