15-21 Historic Log: Value
Array [50]
Range:
Function:
0
*
[0 -
2147483647 ]
View the value of the logged event.
Interpret the event values according to
this table:
Digtal input
Decimal value. See
for
description after
converting to binary
value.
Digital output
(not
monitored in
this SW
release)
Decimal value. See
for description after
converting to binary
value.
Warning word Decimal value. See
16-92 Warning Word
for
description.
Alarm word
Decimal value. See
16-90 Alarm Word
for
description.
Status word
Decimal value. See
for
description after
converting to binary
value.
Control word Decimal value. See
for
description.
Extended
status word
Decimal value. See
for
description.
15-22 Historic Log: Time
Array [50]
Range:
Function:
0 ms
*
[0 - 2147483647
ms]
View the time at which the logged
event occurred. Time is measured in
ms since unit start. The max. value
corresponds to approx. 24 days which
means that the count will restart at
zero after this time period.
6.7.4 15-3* Alarm Log
Parameters in this group are array parameters, where up to
10 fault logs can be viewed. [0] is the most recent logged
data, and [9] the oldest. Error codes, values, and time
stamp can be viewed for all logged data.
15-30 Fault Log: Error Code
Array [10]
Range:
Function:
0
*
[0 - 255 ] View the error code and look up its meaning in
the
Troubleshooting
chapter of the VLT
AutomationDrive Design Guide.
15-31 Alarm Log: Value
Array [10]
Range:
Function:
0
*
[-32767 - 32767 ] View an extra description of the error.
This parameter is mostly used in
combination with alarm 38 ‘internal
fault’.
15-32 Alarm Log: Time
Array [10]
Range:
Function:
0 s
*
[0 - 2147483647 s] View the time when the logged event
occurred. Time is measured in seconds
from unit start-up.
6.7.5 15-4* Unit Identification
Parameters containing read only information about the
hardware and software configuration of the active filter.
15-40 FC Type
Range:
Function:
0
*
[0 - 0 ] View the FC type. The read-out is identical to the
FC 300 Series power field of the type code
definition, characters 1-6.
15-41 Power Section
Range:
Function:
0
*
[0 - 0 ] View the FC type. The read-out is identical to the
FC 300 Series power field of the type code
definition, characters 7-10.
15-42 Voltage
Range:
Function:
0
*
[0 - 0 ] View the FC type. The read-out is identical to the
power field of the type code definition, characters
11-12.
15-43 Software Version
Range:
Function:
0
*
[0 - 0 ] View the combined SW version (or ‘package
version’) consisting of power SW and control SW.
How to Programme
VLT Active Filter AAF 00x