0-12 This Set-up Linked to
Option:
Function:
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
0-13 Readout: Linked Set-ups
Array [5]
Range:
Function:
0
*
[0 - 255 ] View a list of all the set-ups linked by means of
0-12 This Set-up Linked to
. The parameter has one
index for each parameter set-up. The parameter
value displayed for each index represents which
setups are linked to that parameter setup.
Index
LCP value
0
{0}
1
{1,2}
2
{1,2}
3
{3}
4
{4}
Table 6.3 Example: Set-up 1 and Set-up 2 are
linked
0-14 Readout: Edit Set-ups / Channel
Range:
Function:
0
*
[-2147483648 -
2147483647 ]
View the setting of
for each
of the four different communication
channels. When the number is displayed in
hex, as it is in the LCP, each number
represents one channel.
Numbers 1-4 represent a set-up number; ‘F’
means factory setting; and ‘A’ means active
set-up. The channels are, from right to left:
LCP, FC-bus, USB, HPFB1-5.
Example: The number AAAAAA21h means
that the FC bus selected Set-up 2 in
, the LCP selected Set-up 1
and all others used the active set-up.
6.3.4 0-2* LCP Display
Define the variables displayed in the Graphical Local
Control Panel.
NOTE
Please refer to
0-37 Display Text 1
,
0-38 Display Text 2
and
0-39 Display Text 3
for information on how to write display
texts.
0-20 Display Line 1.1 Small
Option:
Function:
Select a variable for display in
line 1, left position.
[0]
None
No display value selected.
[1501]
Running Hours
[1600]
Control Word
Present control word
[1603]
Status Word
Present status word.
[1630]
DC Link Voltage
Intermediate circuit voltage in
the unit.
[1634]
Heatsink Temp.
Present heat sink temperature
of the unit. The cut-out limit is
95 ±5 oC; cutting back in
occurs at 70 ±5° C.
[1635]
Inverter Thermal
Percentage load of the
inverters.
[1636]
Inv. Nom. Current
Nominal current of the unit.
[1637]
Inv. Max. Current
Maximum current of the unit.
[1639]
Control Card Temp.
Temperature of the control
card.
[1660]
Digital Input
Signal states form the 6 digital
terminals (18, 19, 27, 29, 32
and 33). There are 16 bits in
total, but only six of them are
used. Input 18 corresponds to
the leftmost of the used bits.
Signal low = 0; Signal high =
1.
[1666]
Digital Output [bin]
Binary value of all digital
outputs.
[1671]
Relay Output [bin]
[1680]
Fieldbus CTW 1
Control word (CTW) received
from the Bus Master.
[1684]
Comm. Option STW
Extended fieldbus communi-
cation option status word.
[1685]
FC Port CTW 1
Control word (CTW) received
from the Bus Master.
[1690]
Alarm Word
One or more alarms in a Hex
code.
[1691]
Alarm Word 2
One or more alarms in a Hex
code.
[1692]
Warning Word
One or more warnings in a
Hex code.
[1693]
Warning Word 2
One or more warnings in a
Hex code.
How to Programme
VLT Active Filter AAF 00x
56
MG.90.V2.02 - VLT® is a registered Danfoss trademark
6