VLT® 7000 Booster
Programming
004 LCP copy
(LCP COPY)
Value:
✭
No copying (NO COPY)
[0]
Upload all parameters
(UPLOAD ALL PARAMET.)
[1]
Download all parameters
(DOWNLOAD ALL PARAM.)
[2]
Download power-independent par.
(DOWNLOAD SIZE INDEP.)
[3]
Function:
Parameter 004
LCP copy
is used if the integrated
copying function of the control panel is to be used.
This function is used if all parameter Setups are
to be copied from one frequency converter to
another by moving the control panel.
Description of choice:
Select
Upload all parameters
[1] if all parameter values
are to be transmitted to the control panel.
Select
Download all parameters
[2] if all transmitted
parameter values are to be copied to the frequency
converter on which the control panel has been mounted.
Select
Download power-independent par
. [3] if only the
power-independent parameters are to be downloaded.
This is used if downloading to a frequency converter
that has a different rated power than the one from
where the parameter Setup originates.
NB!:
Uploading/Downloading can only be carried
out in the Stop mode.
■
Setup of user-defined readout
Parameter 005
Max. value of user-defined readout
and 006
Unit for user-defined readout
allow users
to design their own readout which can be seen
if user-defined readout has been selected under
display readout. The range is set in parameter 005
Max. value of user-defined readou
t and the unit is
determined in parameter 006
Unit for user-defined
readout
. The choice of unit decides whether the
ratio between the output frequency and the readout
is a linear, square or cubed ratio.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.70.A1.02 - VLT is a registered Danfoss trademark