VLT
®
6000 HVAC
Installation
d [mm]
Comments
Bookstyle
VLT 6002-6005, 200-240 V
100
VLT 6002-6011, 380-460 V
100
Installation on a plane, vertical surface (no spacers)
Compact (all enclosure types)
VLT 6002-6005, 200-240 V
100
VLT 6002-6011, 380-460 V
100
VLT 6002-6011, 525-600 V
100
Installation on a plane, vertical surface (no spacers)
VLT 6006-6032, 200-240 V
200
VLT 6016-6072, 380-460 V
200
VLT 6102-6122, 380-460 V
225
VLT 6016-6072, 525-600 V
200
Installation on a plane, vertical surface (no spacers)
VLT 6042-6062, 200-240 V
225
VLT 6100-6275, 525-600 V
225
Installation on a plane, vertical surface (no spacers)
IP 54 filter mats must be changed when they are dirty.
VLT 6152-6352, 380-460 V
225
Installation on a plane, vertical surface (spacers can be used). IP 54 filter
mats must be changed when they are dirty.
■
Installation of VLT 6400-6550 380-460 V Compact
IP 00, IP 20 and IP 54
Cooling
Side-by-side
All units in the above-mentioned series require a
minimum space of 400 mm above the enclosure
and must be installed on a plane floor. This applies
to both IP 00, IP 20 and IP 54 units.
Gaining access to VLT 6400-6550 requires a
minimum space of 605 mm in front of the frequency
converter.
All IP 00, IP 20 and IP 54 units in the
above-mentioned series can be installed side by side
without any space between them, since these units
do not require cooling on the sides.
■
IP 00 VLT 6400-6550 380-460 V
The IP 00 unit is designed for installation in a cabinet
when installed according to the instructions in the
VLT 6400-6550 Installation Guide MG.56.AX.YY.
Please note, that the same conditions as for NEMA
1/ IP20 and IP54 must be fulfilled.
MG.60.C7.02 - VLT is a registered Danfoss trademark
5