VLT® 5000 Crane
■
Operation & Display
001 LANGUAGE
Value:
✭
English (ENGLISH)
[0]
German (DEUTSCH)
[1]
French (FRANCAIS)
[2]
Spanish (ESPANOL)
[4]
Italian (ITALIANO)
[5]
Function:
The purpose of this parameter is to set the
language to be shown in the display whenever
the LCP control unit is connected.
002 OPERATION SITE
Value:
✭
Remote operation (REMOTE)
[0]
Local operation (LOCAL)
[1]
Function:
The purpose of this parameter is to set the control of
the frequency converter to either
Remote operation
[0]
or
Local operation
[1]. See also parameter 013
Local
control
if
Local operation
[1] is selected.
NB!:
Local control
only is available when
running in FC profile!
Description of choice:
If
Remote operation
[0] is selected, the frequency
converter is controlled via:
1.
The control terminals or via serial communication.
2.
The [START] key. This cannot, however, override
stop commands transmitted via the digital inputs
or via serial communication.
3.
The [STOP/RESET] key, on the condition
that it is active.
If
Local operation
[1], is selected, the frequency
converter is controlled via:
1. The [START] key. This cannot, however, override
stop commands via the digital inputs.
2. The [STOP/RESET] key, on the condition
that it is active.
3.
The [FWD/REV] key, on the condition that
it has been selected as active in parameter
016
Local reversing
[3].
4. Parameter 003
Local reference
where the reference
can be set using the [+] and [-] keys.
5. An external control command that can be
connected to the digital inputs.
NB!:
The [FWD/REV] key is located on the
LCP control unit.
003 LOCAL REFERENCE
Function:
This parameter allows manual setting of the
desired reference value (speed or reference for
the selected configuration).
Description of choice:
Local
[1] must be selected in parameter 002
for this parameter to be used.
In this parameter Data Change Mode is not exited
automatically (after time out).
Local reference cannot be set via the serial
communication port.
007 LCP COPY
Value:
✭
No copying (NO COPY)
[0]
Upload all parameters (UPL. ALL PAR.)
[1]
Download all parameters (DWNL. ALL PAR.)
[2]
Download size-independent parameters
(DWNL. OUTPIND. PAR.)
[3]
Function:
Parameter 007
LCP copy
is used for the LCP
control panel
’
s integral copy function. The function
is used for copying all parameter set-ups from
one frequency converter to another by moving
the detachable LCP control panel.
Description of choice:
Select
Upload all parameters
[1] for transferring
all parameter values to the control panel. Select
Download all parameters
[2] to copy all parameter
values transferred to the frequency converter
to which the control panel is attached. Select
Download size-independent par.
[3] for downloading
the size-independent parameters. This is used
when downloading to a frequency converter with
a different rated power size than the one from
which the parameter setup originates.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.50.N4.02 - VLT is a registered Danfoss trademark
50