VLT® 5000 Crane
LCP - Local Control
Panel
■
Parameter programming
Menu mode is started by pressing the [MENU] key,
which produces the following readout on the display:
50.0 Hz
FREQUENCY
0 KEYB.&DISPLAY
Line 3 on the display shows the parameter
group number and name.
In Menu mode, the parameters are divided
into groups. Selection of parameter group is
effected using the [< >] keys.
The following parameter groups will be accessible:
Group no.
Parameter group
0xx
Operation & Display
1xx
Load & Motor
2xx
References & Limits
3xx
Inputs & Outputs
4xx
Special functions
5xx
Serial communication
6xx
Technical functions
7xx
Crane functions
When the required parameter group has been
selected, each parameter can be chosen by
means of the [+ / -] keys:
FREQUENCY
001 LANGUAGE
ENGLISH
50.0 Hz
The 3rd line of the display shows the parameter
number and name, while the status/value of the
selected parameter is shown in line 4.
Changing data
Regardless of whether a parameter has been
selected under the Quick menu or the Menu mode,
the procedure for changing data will be the same.
Pressing the [CHANGE DATA] key gives access
to changing the selected parameter, following
which the underlining in line 4 will flash on the
display. The procedure for changing data depends
on whether the selected parameter represents a
numerical data value or a text value.
Changing a data value
If the selected parameter is a text value, the text value
is changed by means of the [+ / -] keys.
50.0 Hz
FREQUENCY
001 LANGUAGE
ENGLISH
The bottom display line will show the value that will be
entered (saved) when acknowledgment is given [OK].
Change of numeric data value
If the selected parameter is represented by a numerical
data value, a digit is first chosen using the [< >] keys.
50.0 Hz
SETUP
1
FREQUENCY
130 START FREQUENCY
0
9
.0 HZ
The selected digit can then be changed infinitely
variably using the [+ / -] keys:
50.0 Hz
SETUP
1
FREQUENCY
130 START FREQUENCY
1
0.0 HZ
MG.50.N4.02 - VLT is a registered Danfoss trademark