VLT® 5000 Crane
■
Mains Supply 400 - 500 V
According to international requirements
VLT type
5042
5052
5062
Output current
I
VLT,N
(S3 60%) [A]
(400-500 V)
58
69
85
I
VLT, MAX
(60 s) [A] (400-500 V)
97.6
116.8
135
Output
S
VLT,N
(S3 60%) [kVA]
(400-500 V)
39.2
46.6
57.4
Typical shaft output
P
VLT,N
[kW]
22
30
37
Typical shaft output
P
VLT,N
[HP]
30
41
50
Max. cable cross-section to motor and
brake [mm
2
]/[AWG]
2)3)
IP20
50/0
50/0
Rated input current
I
L,N
(S3 60%) [A] (400 V)
51
62
76
Max. cable cross-section
power[mm
2
]/[AWG]
2)3)
35/2
50/0
50/0
Max. pre-fuses
[-]/UL
1)
[A]
100/100
125/125
150/50
Efficiency
0.96
0,96
0.96
Weight IP 20 SB
[kg]
41
42
43
Power loss at max. load.
1004
1210
1500
Enclosure
IP20
IP20
IP20
1. For type of fuse see section
Fuses
.
2. American wire gauge.
3. Connection stud 1 x M8/2 x M8.
MG.50.N4.02 - VLT is a registered Danfoss trademark
20