
VLT
®
5000 FLUX
Programming
■
Analog Outputs
Analog outputs (terminal 42 and 45).
Analog outputs are current outputs: 0/4 - 20 mA.
Common terminal (terminal 39) is the same terminal and electrical potential for analog common and digital
common connection.
Outputs
terminal no.
42
45
parameter
319
321
Value:
No function
(NO OPERATION)
[0]
✭
[0]
✭
0-100 Hz
⇒
0-20 mA
(0-100 Hz = 0-20 mA)
[1]
[1]
0-100 Hz
⇒
4-20 mA
(0-100 Hz = 4-20 mA)
[2]
[2]
Ref
MIN
- Ref
MAX
⇒
0-20 mA
(REF MIN-MAX = 0-20 mA)
[3]
[3]
Ref
MIN
- Ref
MAX
⇒
4-20 mA
(REF MIN-MAX = 4-20 mA)
[4]
[4]
0 - I
MAX
⇒
0-20 mA
(0-IMAX = 0-20 mA)
[7]
[7]
0 - I
MAX
⇒
4-20 mA
(0-IMAX = 4-20 mA)
[8]
[8]
0 - T
LIM
⇒
0-20 mA
(0-TLIM = 0-20 mA)
[9]
[9]
0 - T
LIM
⇒
4-20 mA
(0-TLIM = 4-20 mA)
[10]
[10]
0 - T
NOM
⇒
0-20 mA
(0-TNOM = 0-20 mA)
[11]
[11]
0 - T
NOM
⇒
4-20 mA
(0-TNOM = 4-20 mA)
[12]
[12]
0 - P
NOM
⇒
0-20 mA
(0-PNOM = 0-20 mA)
[13]
[13]
0 - P
NOM
⇒
4-20 mA
(0-PNOM = 4-20 mA)
[14]
[14]
0 - MAX SPEED
⇒
0-20 mA
(0-MAX SPD. = 0-20 mA)
[15]
[15]
0 - MAX SPEED
⇒
4-20 mA
(0-MAX SPD. = 4-20 mA)
[16]
[16]
+/-160% TORQ
⇒
0-20mA
(+/-160% TORQ= 0-20mA)
[17]
[17]
+/-160% TORQ
⇒
4-20mA
(+/-160% TORQ= 4-20mA)
[18]
[18]
319 Terminal 42 Output
(AO 42 FUNCTION)
Value:
See tabel in section
Analog Outputs.
Function:
The analog output function generates an
analog current 0/4-20 mA.
Description of choice:
See description in section
Analog output.
321 Terminal 45, output
(AO 45 FUNCTION)
Value:
See table in section
Analog outputs.
Function:
The analog output function generates an
analog current 0/4-20 mA.
Description of choice:
See description in section
Analog Outputs.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A6.02 - VLT is a registered Danfoss trademark
95