Motor voltage [V]
states the voltage supplied
to the motor.
DC link voltage [V]
states the intermediate circuit
voltage in the frequency converter.
Thermal load, motor [%]
states the
calculated/estimated thermal load on the
motor. 100% is the cut-out limit.
Thermal load, VLT [%]
states the calculated/estimated
thermal load on the frequency converter.
100% is the cut-out limit.
Hours run [Hours]
states the number of hours that the
motor has run since the latest reset in parameter 619.
Digital input [Binary code]
states the signal states
from the 8 digital terminals (16, 17, 18, 19, 27, 29,
32 and 33) Input 16 corresponds to the bit at the far
left.
’
0
’
= no signal,
’
1
’
= connected signal.
Analog input 53 [V]
states the signal value
on terminal 53.
Analog input 54 [V]
states the signal value
on terminal 54.
Analog input 60 [V]
states the signal value
on terminal 60.
Pulse reference [Hz]
states the possible frequency
in Hz connected to the terminals 17 or 29.
External reference [%]
gives the sum of
the external reference as a percentage (the
sum of analog/pulse/bus).
Status word [Hex]
gives the status word sent
via the serial communication port in Hex code
from the frequency converter.
Brake power/2 min [KW]
states the brake
power transferred to an external brake resistor.
The mean power is calculated continuously
for the latest 120 seconds.
The resistor value must be entered in parameter 401.
Brake power/sec [kW]
states the present brake
power transferred to an external brake resistor.
Stated as an instantaneous value.
The resistor value must be entered in parameter 401.
Heat sink temp [ °C]
states the present heat sink
temperature of the frequency converter. The cut-out
limit is 90 ± 5°C; cutting back in occurs at 60 ± 5°C.
Alarm word [Hex]
indicates one or several
alarms in a Hex code.
Control word [Hex]
indicates the control word for
the frequency converter. See
Serial communication
in the Design Guide for VLT 5000 Process.
Warning word [Hex]
indicates one or more
warnings in a Hex code.
Ext. Status Word [Hex]
indicates one or more
status states in a Hex code.
Digital Output [Bin]
(26, 46)
Communication option card warning [Hex]
gives a warning word if there is a fault on the
communication bus. Is only active if communication
options have been installed. Without communication
options, 0 Hex is displayed.
KTY sensor [ °C]
states the present temperature of
the windings of the motor, when the KTY sensor is
connected to analog input (terminal 54). When the
KTY sensor is not connected, it shows 20°C.
010 Display line 1.1 (DISPLAY LINE 1.1)
011 Display line 1.2 (DISPLAY LINE 1.2)
012 Display line 1.3 (DISPLAY LINE 1.3)
Value:
As for parameter 009
Function:
parameter 010 - 012 is a choice of three different data
values to be shown on the display, line 1 position 1, line
1 position 2 and line 1 position 3, respectively.
For display read-outs, press the [DISPLAY/STATUS]
button. See the sections
Control Panel
and
Display Mode
.
Description of choice:
There is a choice of 32 different data values,
see parameter 009.
Factory setting for each parameter:
Parameter 010 [1]
Reference [%]
Parameter 011 [6]
Motor current [A]
Parameter 012 [8]
Power [kW]
013 Local operation mode
(LOCAL OPER. MODE)
Value:
Local not active (DISABLE)
[0]
✭
LCP control (LCP CONTROL)
[3]
LCP digital control (LCP+DIG CONTROL)
[4]
Function:
This is where the desired function is to be selected if
Local control has been chosen in parameter 002.
See the description of parameter 100.
Description of choice:
If
Local not active
[0] is selected, a possible setting of
Local reference via parameter 003
is blocked.
It is only possible to change to
Local not active
[0]
from one of the other setting options in parameter
✭
= factory setting. () = display text [] = value for use in communication via serial communication port