VLT
®
5000 FLUX
[DISPLAY / STATUS]
selects the mode of display
or for changing back to Display mode from either
the Quick menu mode or the Menu mode.
[QUICK MENU]
programms the parameters that
belong under the Quick menu mode. It is possible
to switch directly between Quick menu mode and
Menu mode.
[MENU]
programms all parameters. It is possible
to switch directly between Menu mode and Quick
menu mode.
[CHANGE DATA
] changes the parameter selected
either in the Menu mode or the Quick menu mode.
[CANCEL]
is used if a change of the selected
parameter is not to be carried out.
[OK]
confirms a change of the parameter selected.
[+/-]
selects parameter and for changing the
chosen parameter or for changing the read out in
line 2.
[<>]
is used for selecting group and to move the
cursor when changing numerical parameters.
Local control keys:
[STOP / RESET]
stops the motor connected or
resetts the frequency converter after a drop-out
(trip). Can be selected via parameter 014 to be
active or inactive. If stop is activated, line 2 will
flash, and [START] must be activated.
[JOG]
overrides the output frequency to a preset
frequency while the key is kept down. Can be
selected via parameter 015 to be active or inactive.
[FWD / REV]
changes the direction of rotation of
the motor. Forward or Reverse direction is indicated
by means of the arrow on the display although only
in Local. Parameter 016 selects the function to be
active or inactive, depending on parameter 506.
[START]
is used for starting the frequency
converter after stop via the "Stop" key. Is always
active, but cannot override a stop command given
via the terminal strip.
NB!:
If the keys for local control have been selected
as active, they will remain active both when
the speed has been set for
Local Control
and
for
Remote Control
via parameter 002. [Fwd/rev]
is only active in Local operation.
NB!:
If no external stop function has been selected
and the [Stop] key has been selected as
inactive, the motor can be started and can only
be stopped by disconnecting the voltage to the motor.
■
Display read-out state
The display read-out state can be varied depending
on whether the frequency converter is in normal
operation or is being programmed.
■
Display mode
In normal operation, up to 4 different operating
variables can be indicated continuously: In
line 1 and 2 the present operating status or
alarms, and warnings in line 4.