VLT
®
5000 FLUX
Description of choice:
If
Reset
[1] has been selected and when the [OK] key
is pressed, the hours-run counter of the frequency
converter is reset. This parameter cannot be
selected via the serial port, RS 485.
NB!:
When the [OK] key has been activated, the
reset has been carried out.
620 OPERATION MODE
Value:
✭
Normal function (NORMAL OPERATION)
[0]
Initialisation (INITIALIZE)
[3]
Function:
Operation mode In addition to its normal function,
this parameter can be used for two different tests.
Also, all parameters (except parameters 603-605) can
be initialized. This function will not become active
until the mains supply to the frequency converter has
been turned off and then turned on again.
Description of choice:
Normal function
[0] is selected for normal operation
with the motor in the selected application.
Initialisation
[3] is selected if the factory setting of
the unit is desired without resetting parameters
500, 501 + 600 - 605 + 615 - 617.
⇒
The motor must be stopped before initialisation
can be carried out.
Procedure for initializing:
1. Select Initialisation.
2. Press the [OK] key.
3. Cut off the mains supply and wait for the
light in the display to go out.
4. Connect to mains.
Manual initialisation can be carried out by holding down
three keys at the same time as the mains voltage is
connected. Manual initialisation sets all parameters to
the factory setting, except 600-605. The procedure
for manual initialisation is as follows:
1. Disconnect the mains voltage and wait for the
light in the display to disappear.
2. Hold down [DISPLAY/[MENU]+[OK] while
at the same time connecting the mains supply. The
display will now read MANUAL INITIALIZE.
3. When the display reads UNIT READY, the frequency
converter has been initialized.
Parameter no.
Description
Nameplate
Display text
621
VLT type
(VLT TYPE)
622
Power section
(POWER SECTION)
623
VLT ordering number
(VLT ORDERING NO)
624
Software version number
(SOFTWARE VERSION)
625
LCP identification number
(LCP ID NO)
626
Database identification number
(PARAM DB ID)
627
Power section identification number
(POWER UNIT DB ID)
628
Application option type
(APP. OPTION)
629
Application option ordering number
(APP. ORDER NO)
630
Communication option type
(COM. OPTION)
631
Communication option ordering number
(COM. ORDER NO)
Function:
The key data of the unit can be read out via the
display or the serial communication port.
Description of choice:
VLT type, parameter 621:
VLT Type indicates the unit size and basic
function concerned.
For example: VLT 5008 380-500 V.
Power section, parameter 622:
The power section states the given power
section being used.
For example: Extended with brake.
VLT ordering number, parameter 623:
Ordering number gives the ordering number
of the VLT type in question.
For example: 175Z0072.
Software version number, parameter 624:
Software version gives the version number.
For example: V 3,10.
LCP identification number, parameter 625:
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A6.02 - VLT is a registered Danfoss trademark
118