VLT
®
4000 VT
203 Reference site
(REFERENCE SITE)
Value:
✭
Hand/Auto linked reference
(LINKED TO HAND/AUTO)
[0]
Remote reference (REMOTE)
[1]
Local reference (LOCAL)
[2]
Function:
This parameter determines the location of the
active reference. If
Hand/Auto linked reference
[0]
is selected, the resulting reference will depend on
whether the AFD is in Hand or Auto mode.
The table shows which references are active when
Hand/Auto linked reference
[0],
Remote reference
[1] or
Local reference
[2] has been selected. The Hand mode
or Auto mode can be selected via the control keys or
via a digital input, parameters 300-307
Digital inputs
.
Reference
handling
Hand mode
Auto mode
Hand/Auto [0]
Local ref. active
Remote ref. active
Remote [1]
Remote ref. active
Remote ref. active
Local [2]
Local ref. active
Local ref. active
Description of choice:
If
Hand/Auto linked reference
[0] is chosen, the motor
speed in Hand mode will be decided by the local
reference, while in Auto mode it depends on remote
references and any setpoints selected.
If
Remote reference
[1] is selected, the motor speed will
depend on remote references, regardless of whether
Hand mode or Auto mode has been chosen.
If
Local reference
[2] is selected, the motor speed
will only depend on the local reference set via the
control panel, regardless of whether Hand mode
or Auto mode has been selected.
204 Minimum reference, Ref
MIN
(MIN. REFERENCE)
Value:
Parameter 100
Configuration = Open loop
[0].
0.000 - parameter 205 Ref
MAX
✭
0.000 Hz
Parameter 100
Configuration = Closed loop
[1].
-Par. 413
Minimum feedback
- par. 205 Ref
MAX
✭
0.000
Function:
The
Minimum reference
gives the minimum value
that can be assumed by the sum of all references.
If
Closed loop
has been selected in parameter 100
Configuration
, the minimum reference is limited by
parameter 413
Minimum feedback
.
Minimum reference is ignored when the local reference
is active (parameter 203
Reference site
). The unit for
the reference can be seen from the following table:
Unit
Par. 100
Configuration = Open loop
Hz
Par. 100
Configuration = Closed loop
Par. 415
Description of choice:
Minimum reference is set if the motor is to run
at a minimum speed, regardless of whether
the resulting reference is 0.
205 Maximum reference, Ref
MAX
(MAX. REFERENCE)
Value:
Parameter 100
Configuration = Open loop
[0]
Parameter 204
Ref
MIN
- 1000.000 Hz
✭
60 Hz
Parameter 100
Configuration = Closed loop
[1]
Par. 204
Ref
MIN
- par. 414
Maximum feedback
✭
60 Hz
Function:
The
Maximum reference
gives the maximum value
that can be assumed by the sum of all references.
If
Closed loop
[1] has been selected in parameter
100
Configuration
, the maximum reference cannot be
set above parameter 414
Maximum feedback
. The
Maximum reference
is ignored when the local reference
is active (parameter 203
Reference site
).
The reference unit can be determined on the
basis of the following table:
Unit
Par. 100
Configuration = Open loop
Hz
Par. 100
Configuration = Closed loop
Par. 415
Description of choice:
Maximum reference
is set if the motor speed is not
to exceed the set value, regardless of whether the
resulting reference is higher than
Maximum reference
.