VLT
®
4000 VT
■
Line Supply, 3 x 525 - 600 V
Output
VLT type
4006
4008
4011
Output Current
I
VLT,N
[A] (550 V)
6.4
9.5
11.5
I
VLT, MAX
(60 s) [A] (550 V)
7.0
10.5
12.7
I
VLT, N
[A] (575 V)
6.1
9.0
11.0
I
VLT, MAX
(60 s) [A] (575 V)
6.7
9.9
12.1
Output
S
VLT,N
[kVA] (550 V)
6.1
9.0
11.0
S
VLT,N
[kVA] (575 V)
6.1
9.0
11.0
Typical shaft output
P
VLT,N
[kW]
4
5.5
7.5
Typical shaft output
P
VLT,N
[HP]
5
7.5
10
Max. copper cable cross-section to
motor and loadsharing
4)
[mm
2
/AWG]
2)
4/10
4/10
4/10
Input
Rated Input Current
I
VLT,N
[A] (550 V)
6.2
9.2
11.2
I
VLT, N
[A] (600 V)
5.7
8.4
10.3
Max. copper cable cross-section
power, NEMA 1
4)
[mm
2
/AWG]
2)
4
10
4
10
4
10
Efficiency
3)
0.96
0.96
0.96
Max. pre-fuses (mains)
1)
[-]/UL
1)
[A]
8
10
15
Weight IP20 / NEMA 1
[kg]
10.5
10.5
10.5
[lbs]
23.1
23.1
23.1
Estimated power loss at max. load
[W]
161
238
288
Enclosure
IP 20 and NEMA 1
1. See section
Fuses.
2. American Wire Gauge (AWG).
3. Measured using 100 ft screened motor cables at rated load and rated frequency.