Parameter 614 Data log: DC-link voltage:
This gives the latest log data for the intermediate
circuit voltage.
615 Fault log: Error code
(F. LOG: ERROR CODE)
Value:
[Index 1-10]
Error Code: 0 - 99
Function:
This parameter makes it possible to see the reason
why a trip (cut-out of the VLT AFD) occurs. 10
[1-10] log values are stored.
The lowest log number [1] contains the latest/most
recently saved data value; the highest log number
[10] contains the oldest data value.
If there is a trip on the VLT 4000 VT, it is possible
to see its cause, the time and possibly the values
for output current or output voltage.
Description of choice:
Stated as an error code in which the number refers
to a table in
List of warnings and alarms
.
The fault log is only reset after manual initialization.
(See
Manual initialization
).
616 Fault log: Time
(F. LOG: TIME)
Value:
[Index 1-10]
Hours: 0 - 130,000.0
Function:
This parameter makes it possible to see the total number
of hours run in connection with the 10 latest trips.
10 [1-10] log values are stored. The lowest log
number [1] contains the latest/most recently saved
data value, while the highest log number [10]
contains the oldest data value.
Description of choice:
The fault log is only reset after manual initialization.
(See
Manual initialization
).
617 Fault log: Value
(F. LOG: VALUE)
Value:
[Index 1 - 10]
Value: 0 - 9999
Function:
This parameter makes it possible to see the value at
which a trip occurred. The unit of the value depends on
the alarm active in parameter 615
Fault log: Error code
.
Description of choice:
The fault log is only reset after manual initialization.
(
See Manual initialization
).
618 Reset of kWh counter
(RESET KWH COUNT)
Value:
✭
No reset (DO NOT RESET)
[0]
Reset (RESET COUNTER)
[1]
Function:
Reset to zero of parameter 602
kWh counter.
Description of choice:
If Reset [1] has been selected and when the
[OK] key is pressed, the kWh counter of the
AFD is reset. This parameter cannot be selected
via the serial port, RS 485.
NOTE
When the [OK] key has been activated, the
reset has been carried out.
619 Reset of hours-run counter
(RESET RUN. HOUR)
Value:
✭
No reset (DO NOT RESET)
[0]
Reset (RESET COUNTER)
[1]
Function:
Reset to zero of parameter 601
Hours-run
.
Description of choice:
If Reset [1] has been selected and when the
[OK] key is pressed, parameter 601
Hours-run
is reset. This parameter cannot be selected
via the serial port, RS 485.