Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
130BB934.10
Function
Setting
Parameter 5-10 Ter
minal 18 Digital
Input
[8] Start
Parameter 5-11 Ter
minal 19 Digital
Input
[10]
Reversing*
Parameter 5-12 Ter
minal 27 Digital
Input
[0] No
operation
Parameter 5-14 Ter
minal 32 Digital
Input
[16] Preset
ref bit 0
Parameter 5-15 Ter
minal 33 Digital
Input
[17] Preset
ref bit 1
Parameter 3-10 Pre
set Reference
Preset ref. 0
Preset ref. 1
Preset ref. 2
Preset ref. 3
25%
50%
75%
100%
*=Default value
Notes/comments:
Table 17.7 Start/Stop with Reversing and 4 Preset Speeds
17.4 External Alarm Reset
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB928.10
Function
Setting
Parameter 5-11 T
erminal 19
Digital Input
[1] Reset
*=Default value
Notes/comments:
Table 17.8 External Alarm Reset
17.5 Speed Reference with Manual
Potentiometer
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A53
U - I
≈ 5kΩ
130BB683.10
Function
Setting
Parameter 6-10 T
erminal 53 Low
Voltage
0.07 V*
Parameter 6-11 T
erminal 53 High
Voltage
10 V*
Parameter 6-14 T
erminal 53 Low
Ref./Feedb. Value
0 RPM
Parameter 6-15 T
erminal 53 High
Ref./Feedb. Value
1500 RPM
*=Default value
Notes/comments:
Table 17.9 Speed Reference (Using a Manual Potentiometer)
Application Examples
VLT
®
Parallel Drive Modules
154
Danfoss A/S © 6/2016 All rights reserved.
MG37N102
17
17