Parameters
130BB927.10
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A53
U - I
4 - 20mA
+
-
Function
Setting
Parameter 6-12 T
erminal 53 Low
Current
4 mA*
Parameter 6-13 T
erminal 53 High
Current
20 mA*
Parameter 6-14 T
erminal 53 Low
Ref./Feedb. Value
0 RPM
Parameter 6-15 T
erminal 53 High
Ref./Feedb. Value
1500 RPM
*=Default value
Notes/comments:
Table 17.4 Analog Speed Reference (Current)
17.3 Start/Stop
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB802.10
Function
Setting
Parameter 5-10 T
erminal 18
Digital Input
[8] Start*
Parameter 5-12 T
erminal 27
Digital Input
[0] No
operation
Parameter 5-19 T
erminal 37 Safe
Stop
[1] Safe
Torque Off
Alarm
*=Default value
Notes/comments:
If
parameter 5-12 Terminal 27
Digital Input
is set to
[0] No
operation
, a jumper wire to
terminal 27 is not needed.
Table 17.5 Start/Stop Command with Safe Torque Off
130BB805.11
Speed
Start (18)
Illustration 17.1 Start/Stop with Safe Torque Off
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB803.10
Function
Setting
Parameter 5-10 T
erminal 18
Digital Input
[9] Latched
Start
Parameter 5-12 T
erminal 27
Digital Input
[6] Stop
Inverse
*=Default value
Notes/comments:
If
parameter 5-12 Terminal 27
Digital Input
is set to
[0] No
operation
, a jumper wire to
terminal 27 is not needed.
Table 17.6 Pulse Start/Stop
Speed
130BB806.10
Latched Start (18)
Stop Inverse (27)
Illustration 17.2 Latched Start/Stop Inverse
Application Examples
Design Guide
MG37N102
Danfoss A/S © 6/2016 All rights reserved.
153