background image

The instructions provide information about installation of the

mounting adapter for exchanging a VLT

®

 2800 with a VLT

®

Midi Drive FC 280.

Only Danfoss authorized, qualified personnel is allowed to
install this equipment. The personnel must be familiar with the
instructions and safety measures described in the

VLT

®

 Midi Drive FC 280 Service Guide

.

Items Supplied

Four different mounting adapters are available. Each adapter
comes with either 4 or 8 screws, depending on the type of
adapter.

Mounting adapter 1

-

4 screws size M4x20

Mounting adapter 2

-

4 screws size M4x20

-

4 screws size M5x20

Mounting adapter 3

-

4 screws size M5x20

Mounting adapter 4

-

4 screws size M6x20

Mounting adapter

Enclosure

Corresponding

VLT

®

 2800

Ordering number

Adapter A

K1

Size A

132B0363

Adapter B

K1/K2

Size B

132B0364

Adapter C

K2/K3

Size C

132B0365

Adapter D

K4/K5

Size D

132B0366

Tools Required

Screwdrivers:

-

T20

Safety Instructions

WARNING

DISCHARGE TIME

The frequency converter contains DC-link capacitors, which
can remain charged even when the frequency converter is
not powered. High voltage can be present even when the
warning LED indicator lights are off. Failure to wait the
specified time after power has been removed before
performing service or repair work can result in death or
serious injury.

Stop the motor.

Disconnect AC mains and remote DC-link supplies,
including battery back-ups, UPS, and DC-link
connections to other frequency converters.

Disconnect or lock PM motor.

Wait for the capacitors to discharge fully. The
minimum waiting time is specified in 

Table 1.1

.

Before performing any service or repair work, use
an appropriate voltage measuring device to make
sure that the capacitors are fully discharged.

Voltage [V]

Power range

[kW (hp)]

Minimum waiting time

(minutes)

200–240

0.37–3.7 (0.5–5)

4

380–480

0.37–7.5 (0.5–10)

4

11–22 (15–30)

15

Table 1.1 Discharge Time

Installation

NOTICE

For dimensions of the various adapter plates, refer to

Illustration 1.1

 to 

Illustration 1.4

.

1.

Using the mounting holes and screws from the old
frequency converter, securely fasten the adapter
plate.

2.

Mount the supplied screws.

3.

Position the frequency converter and slide it onto the
adapter plate screws.

Installation Instructions

Mounting Adapter to VLT

®

 2800

VLT

®

 Midi Drive FC 280

Danfoss A/S © 02/2016 All rights reserved.

MI07F102

Reviews: