Illustration 78: Dimensions of the Mounting Holes for VACON
®
NXS/NXP AC Drive, FR11 Standalone
Table 39: Dimensions of the Mounting Holes in mm (inch) for VACON
®
NXS/NXP AC Drive, FR11 Standalone
Drive type
E1Ø, grommet in‐
side diameter
(1)
E1Ø, gland
plate hole
E2Ø, grommet in‐
side diameter
(1)
E2Ø, gland
plate hole
E3Ø, mounting
holes for fixing to
floor
•
0590 5–
0730 5
•
0460 6–
0590 6
4 x 21
(4 x 0.83)
4 x 28
(4 x 1.10)
8 x 48
(8 x 1.89)
8 x 60
(8 x 2.36)
9 x 11
(9 x 0.43)
1
Same as maximum cable thickness. NOTE! Cable clamps have 40 mm internal diameter. The clamps are used for 360 degree grounding of the shield. Exposing the cable shield
decreases outer diameter of the cable so the recommended 3x185+95 mm
2
MCCMK motor cables fit in the clamp.
12.3 Cable and Fuse Sizes
12.3.1 List of Cable and Fuse Size Information
This topic lists the links to find the cable and fuse size tables for VACON™ NXS and NXP Air Cooled AC Drive.
Use external gG/gL or T/J fuses for overload and short-circuit protection.
•
12.3.2 Cable and Fuse Sizes for 208–240 V and 380–500 V, FR4 to FR9
•
12.3.4 Cable and Fuse Sizes for 525–690 V, FR6 to FR9
•
12.3.6 Cable and Fuse Sizes for 380–500 V, FR10 to FR11 Standalone
•
12.3.8 Cable and Fuse Sizes for 525–690 V, FR10 to FR11
For AC Drives in North America, see:
Specifications
Operating Guide | VACON® NXS/NXP Air-cooled
AQ275638903263en-000301 / DPD00910