Illustration 12: Minimum Clearances around the AC Drive
A
The minimum distance to the side walls or adjacent
components
B
The minimum distance from the top of the cabinet
C
Free space in front of the cabinet
Table 8: Minimum Clearances around the AC Drive in mm (in inch)
Drive type
A
B
C
0385 5–0730 5
0261 6–0590 6
20
(0.79)
200
(7.87)
800
(31.50)
Table 9: Required Cooling Air
Drive type
The quantity of cooling air [m
3
/h]
The quantity of cooling air [CFM]
0385 5–0520 5
0261 6–0416 6
2000
900
0590 5–0730 5
0460 6–0590 6
3000
1765
For more information on the power losses in all operating conditions, see
5.3 Installation Sequence
5.3.1 Installation Sequence for Wall-mounted AC Drives
Use these instructions to install the VACON
®
NX Wall-mounted AC Drive or VACON
®
NX Inverter FI4–FI8.
Procedure
Select the mounting option:
Horizontal
AQ275638903263en-000601 / DPD00910
36 | Danfoss A/S © 2022.12
Mounting the Unit