8.7.5.2 Uploading Parameters to Control Panel (Up To Keypad, S6.3.2)
Context:
Use this function to upload all parameter groups to the control panel when the AC drive is stopped.
Procedure
1. In the Copy parameters (
S6.3
) subpage, find the
Up to keypad
page (
S6.3.2
).
2. Push the Menu button Right.
3. To go to the edit mode, push the Menu button Right.
All param.
starts to blink.
4. To accept the selection, push the [enter] button.
5. Wait until
OK
shows on the display.
8.7.5.3 Downloading Parameters to Drive (Down From Keypad, S6.3.3)
Context:
Use this function to download 1 or all parameter groups from the control panel to an AC drive when the AC drive is stopped.
Procedure
1. In the Copy parameters (
S6.3
) subpage, find the
Down from keypad
page (
S6.3.3
).
2. Push the Menu button Right.
3. To go to the edit mode, push the Menu button Right.
4. Use the Browser buttons to select 1 of these 3 options:
- All parameters (
All param.
)
- All parameters but the motor nominal value parameters (
All. no motor
)
- Application parameters
5. To accept the selection, push the [enter] button.
6. Wait until
OK
shows on the display.
8.7.5.4 Activating or Deactivating the Automatic Parameter Back-up (P6.3.4)
Context:
Use these instructions to activate or deactivate the parameter back-up.
Prerequisites:
When the application is changed, the parameters in the parameter settings on page S6.3.1 are deleted. To copy parameters from one
application to a different application, first upload them to the control panel.