8.4.6 Special Functions in Keypad Control Menu
8.4.6.1 Selecting the Keypad as the Control Mode
Context:
This is a special function only available in menu M3.
Prerequisites:
Make sure to be in the menu M3 and control mode is other than keypad.
Procedure
1. Do one of the following options:
Keep the Start button pushed down for 3 s when the motor is in RUN state.
Keep the Stop button pushed down for 3 s when the motor is stopped.
In other menu than M3, when the keypad is not the active control mode and the start button is pushed, an error message
Keypad
Control NOT ACTIVE
shows. In some applications this error message is not shown.
The keypad is selected as the control mode and the current frequency reference and direction is copied to the control
panel.
8.4.6.2 Copying the Frequency Reference Set to the Control Panel
Context:
These are special functions only available in menu M3.
Use these instructions to copy the frequency reference set from I/O or fieldbus to control panel.
Prerequisites:
Make sure to be in menu M3 and that the control mode is other than keypad.
Procedure
1. Keep the [enter] button pushed down for 3 s.
In other menu than M3, when the keypad is not the active control mode and the start button is pushed, an error message
Keypad
Control NOT ACTIVE
shows.
8.5 Using the Active Faults Menu (M4)
8.5.1 Finding the Active Faults Menu
Context:
The Active faults menu shows a list of active faults. When there are no active faults, the menu is empty.
For more information on the fault types and how to reset faults, see
11.1 General Information on Fault Tracing
. For the fault codes, possible causes and information on how to correct the fault, see the Faults and Alarms section.
Using the Control Panel
Operating Guide | VACON® NXI Inverters FI9-FI14
AQ304441431479en-000101 / DPD00909| 63
Danfoss A/S © 2019.11
Summary of Contents for VACON NXP FI10
Page 1: ...Operating Guide VACON NXI Inverters FI9 FI14...
Page 2: ......