Technical item or function
Technical data
Protections
Overvoltage protection
NX_5: 911 V DC; NX_6: 1200 V DC
Undervoltage protection
NX_5: 333 V DC; NX_6: 461 V DC
Ground fault protection
If there is ground fault in motor or motor cable, only the inverter is
protected
Motor phase supervision
Trips if any of the output phases is missing
Overcurrent protection
Yes
Unit overtemperature protection
Yes
Motor overload protection
Yes
Motor stall protection
Yes
Motor underload protection
Yes
Short-circuit protection of +24 V
and +10 V reference voltages
Yes
1
The voltage ripple of the inverter supply voltage, formed in rectification of the electric network's alternating voltage in basic frequency.
12.8 DC Currents, Supply Voltage 465–800 V DC
Table 29: DC Currents of VACON
®
NX, Supply Voltage 465–800 V DC
Enclosure size
I
N
(output)
Motor cos
I
DC
(input)
FI9
170
0.89
198
205
0.89
239
261
0.89
304
300
0.89
350
FI10
385
0.9
454
460
0.9
542
520
0.9
613
FI12
590
0.9
695
650
0.9
766
730
0.91
870
820
0.91
977
920
0.91
1096
1030
0.91
1227
FI13
1150
0.91
1370
1300
0.91
1549
1450
0.91
1727
Specifications
Operating Guide | VACON® NXI Inverters FI9-FI14
AQ304441431479en-000101 / DPD00909| 131
Danfoss A/S © 2019.11