12.4.2 Cable Sizes for 465–800 V DC (380–500 V AC)
Table 19: Cable Sizes for 465–800 V DC (380–500 V AC)
Enclosure size
(1)
Drive type
I
L
[A]
Supply cable Cu [mm
2
]
Motor cable [mm
2
]
(2)
FI9
NXI_0168 5
170
2×(1×24)
(3)
Cu: 3×95+50
Al: 3×120+70
NXI_0205 5
205
2×(1×24)
(3)
Cu: 3×150+70
Al: 3×240Al+72Cu
NXI_0261 5
261
3×(1×24)
(3)
Cu: 3×185+95
Al: 2×(3×120+70)
NXI_0300 5
300
6×(1×24)
(3)
Cu: 2×(3×120+70)
Al: 2×(3×185Al+57Cu)
FI10
NXI_0385 5
385
5×40
(4)
Cu: 2×(3×120+70)
Al: 2×(3×185Al+57Cu)
NXI_0460 5
460
5×40
(4)
Cu: 2×(3×150+70)
Al: 2×(3×240Al+72Cu)
NXI_0520 5
520
6×40
(4)
Cu: 2×(3×185+95)
Al: 2×(3×300Al+88Cu)
FI12
(5)
NXI_0590 5
590
5×40
(4)
Cu: 2×(3×240+120)
Al: 4×(3×120Al+41Cu)
NXI_0650 5
650
5×40
(4)
Cu: 4×(3×95+50)
Al: 4×(3×150Al+41Cu)
NXI_0730 5
730
5×40
(4)
Cu: 4×(3×120+70)
Al: 4×(3×185Al+57Cu)
NXI_0820 5
820
5×40
(4)
Cu: 4×(3×150+70)
Al: 4×(3×185Al+57Cu)
NXI_0920 5
920
5×40
(4)
Cu: 4×(3×150+70)
Al: 4×(3×240Al+72Cu)
NXI_1030 5
1030
6×40
(4)
Cu: 4×(3×185+95)
Al: 4×(3×300Al+88Cu)