10.455 (ID 1092) Master Follower Mode 2
Location in the menu:
P2.2.7.31
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to select the digital input signal that activates the second Master Follower mode. Select the digital input to acti-
vate the second Master Follower mode selected by parameter
ID 1093
.
10.456 (ID 1093) Master Follower Mode 2 Selection
Location in the menu:
P2.11.7
(Multi-purpose Control Application)
Use this parameter to select the Master Follower function.
Select Master Follower mode 2 that is used when the DI is activated. When Follower is selected, the Run Request command is moni-
tored from Master and all other references are selectable by parameters.
10.457 (ID 1177) Run Enable Indication
Location in the menu:
2.7.47
Use this parameter to select the response for the Run Enable low signal. The drive loses ready status regardless of what is selected
here.
Selection number
Selection name
0
No Action
1
Warning
2
Fault
10.458 (ID 1209) Input Switch Acknowledgement
Location in the menu:
P2.2.7.32
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to select the digital input signal that acknowledges the status of the input switch.
The input switch is normally a switch fuse unit or main contactor with which the power is fed to the drive. If the input switch ac-
knowledgement is missing, the drive trips at Input switch open fault (F64).
10.459 (ID 1210) External Brake Acknowledgement
Location in the menu:
P2.2.7.24
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to select the digital input signal that acknowledges the status of the external brake.
Connect this digital input signal to an auxiliary contact of the mechanical brake. If the brake opening command is given, but the
contact of the brake feedback signal does not close in given time, a mechanical brake fault shows (fault code 58).
10.460 (ID 1213) Quick Stop
Location in the menu:
P2.2.7.30
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to select the digital input signal that activates the quick stop function.
This parameter indicates to the drive that the external quick stop circuit has stopped the machine. Select the digital input to acti-
vate the quick stop input to the drive. When the digital input is low, the drive stops as per the parameter definition of
ID 1276Quick
stop mode
and indicates the warning code A63.
10.461 (ID 1217) ID Bit Free DO1
Location in the menu:
P2.3.1.6
(Multi-purpose Control Application)
Use this parameter to select the signal that controls the digital output.
Set the parameter in format xxxx.yy where xxxx is the ID number of a signal and yy is the bit number. For example, the value for DO
control is 43.06. 43 is the ID number of Status Word. So the digital output is ON when bit number 06 of Status Word (ID number 43)
that is, Run Enable is on.
10.462 (ID 1218) DC Ready Pulse
Location in the menu:
P2.3.3.29
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to select the digital input signal that enables charging of the inverter drive through an input switch.
Charge DC. Used to charge the inverter drive through an input switch. When the DC-link voltage is above the charging level, a 2
second pulse train is generated to close the input switch. The pulse train is OFF when the input switch acknowledgement goes high.
AB296635287482en-000301 / DPD00903 | 283