f
fn
ID706=40%
0
IT
100%
A
B
C
e
3
0
b
u
0
6
0
Illustration 73: The Motor Thermal Current IT Curve
A
P
Cooling
B
Overload area
C
Corner frequency
10.339 (ID 707) Motor Thermal Time Constant
Location in the menu:
P2.7.11
(Standard Application, Local/Remote Control Application, Multi-step Speed Control Application, PID
Control Application, Multi-purpose Control Application, Pump and Fan Control Application
Use this parameter to set the motor thermal time constant.
This time can be set between 1–200 minutes.
The time constant is the time within which the calculated thermal stage has reached 63% of its final value. The final thermal stage
equals to running the motor continuously with nominal load at nominal speed. The length of the time constant is in relation with
the dimension of the motor. The bigger the motor, the longer the time constant.
In different motors, the motor thermal time constant is different. It also changes between different motor manufacturers. The de-
fault value of the parameter changes from dimension to dimension.
The t6-time is the time in seconds that the motor can safely operate at 6 times the rated current. It is possible that the motor manu-
facturer gives the data with the motor. Use this information to set the time constant parameter. Usually, the motor thermal time
constant in minutes is 2*t6. When the drive is in the
STOP
state, the time constant is internally increased to 3 times the set parame-
ter value, because the cooling operates based on convection.
AB296635287482en-000301 / DPD00903
252 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide
Summary of Contents for VACON NX
Page 1: ...Application Guide VACON NX All in One drives danfoss com...
Page 2: ......